Operation and maintenance instructions
Series PME CANopen proportional pressure
regulator
5000054187
Ver. 01
57
This is a useful way to verify that the regulated pressure is within a predetermined accuracy range
or not.
11.5.1.16.
2013h Lower limit window control
This object sets the lower differential for the pressure windows mode in the unit of measure of the
Regulator, it must be a positive value and less than the "Upper limit windows control" parameter.
11.5.1.17.
2014h Upper limit window control
This object sets the higher differential for the pressure windows mode in the unit of measure of the
Regulator, it must be a positive value and greater than the "Lower limit windows control" parameter
11.5.1.18.
2015h Use profile CiA 408
This object allows you to enable / disable the CiA 408 profile. If enabled, the operating status will
follow the state machine specified in the profile with the use of objects 6040h Control Word and
6041h Status Word.
11.5.1.19.
2016h Enable Termination Resistance
This object allows you to enable / disable the termination resistor inside the device. This object must
be enabled if the regulator is the last node of the CANopen line. This enables a 120 ohm resistor in
parallel to the CAN lines, as shown below.
120 ohm
5
4
CAN_H
CAN_L