11.
CANopen pressure regulator
11.1.
Configuration via EDS file
To configure the PME in a CANopen network it is necessary to import the EDS file. The configuration
file describes the characteristics of the CANopen controller and its configuration. The EDS file is
available on the Camozzi website at the following address:
http://catalogue.camozzi.com/Downloads
11.2.
Address and baud rate
The PME CANopen must have a unique address (range 1 - 127) to be correctly identified on the
network and the communication speed (Baud rate) must be set.
To connect the PME to the CANopen bus use a five-pole cable and preferably shielded. The
maximum length of the CANopen line depends on the baud rate (transmission speed) used as
indicated in the following table.
BAUD RATE [kbits/s]
MAXIMIMUN LENGHT OF THE
SEGMENT [m]
10
5000
20
2500
50
1000
125
500
250
250
500
100
800
50
1000
25