INSTRUCTIONAL MANUAL
2750L-P/4500L-P/6000L-P
August, 2001
Rev. K
-138-
The following screen appears for a short time:
Test
A,
B,
C
CLR
to
Reselect
The next screen is:
Apply
Nom
output
Press
ENT
When ENT is selected the following screen appears;
Press
MNU
to
Select
Test
The MNU screen has two lines of selection shown at a time.
There are three different types of operations that can be selected from the MENU screen. If the word MENU appears
for the items selected, another MENU screen will be displayed. If the word Test appears for the item selected, the test
will start. The display will return to the previous screen if the word RETURN appears for the item selected.
The Main Menu will appears as follows:
1 = Normal Menu
2 = Emergency Menu
3 = Abnormal Menu
4 = Return
If Key 1 is selected "Normal Menu" from the Main Menu, the following Menu will appear:
1 = Volt/Freq Menu
2 = Unbalance Test
3 = Volt Mod Test
4 = Power Int Test
5 = Volt Surge Test
6 = Wave Dist Test
7 = Freq Mod Test
8 = Return
If Key 2 is selected "Emergency Menu" from the Main Menu, the following Menu will appear:
1 = Emg V/F Menu
2 = Emg Unbal Test
3 = Return
If Key 3 is selected "Abnormal Menu" from the Main Menu, the following Menu will appear:
1 = Ab Volt Menu
2 = Ab Vunder Test
3 = Ab Vsurge Test
4 = Return
If Key 1 is selected "Volt/Freq Menu" from the Normal Menu, the following Menu will appear: