-29-
1. Loosen the inlet (IN) pressure tap by turning screw
counterclockwise. See (A).
2. Attach manometer using a 1/4” (6 mm) I.D. hose. . Light
pilot and burner. Check pressure to ensure it is between
the minimum and maximum recommended pressure
settings.
3. Turn off burner and pilot.
4. Disconnect hose and tighten the inlet (IN) pressure tap
by turning screw clockwise. Screw should be snug. Do
not over tighten.
5. Relight pilot and burner. Then reattach manometer to the inlet pressure tap (A) to verify the tap is completely
sealed. Manometer should read no pressure.
MANIFOLD PRESSURE TEST
1. Light pilot.
2. Loosen manifold (OUT) pressure tap by turning screw counter-clockwise (see (B).
3. Attach manometer to pressure tap using a 1/4” (6 mm) I.D. hose.
4. Light burner. Check manometer reading.
5. Turn burner and pilot off.
6. Disconnect manometer hose and tighten the manifold (OUT) pressure tap by turning screw clockwise. Screw
should be snug. Do not over tighten.
7. Attach the manometer to the manifold pressure tap (B) to verify it is completely sealed. The manometer
should read no pressure when pilot and burner are on.
Adjustment
PRESSURE TESTING
NOTE: The fireplace and its main gas valve must be disconnected from the gas supply piping system during any
pressure testing of the system at test pressures in excess of 1/2 psi (3.5 kPa).
INLET PRESSURE TEST
NOTE: Make sure to apply these incoming pressure test with all other gas fireplaces on, or at full capacity in the
house for proper pressure reading.
A
B
CAUTION: If the inlet pressure reading is too high or too low, contact the gas company. Only a qualified gas
service technician should adjust incoming gas pressure.
CAUTION: Pressure check taps for manifold (outgoing) and inlet (incoming) pressure have been incorporated
into the valve. The pressure tap marked OUT measures outgoing pressure. The pressure tap marked IN measures
incoming pressure.
Inlet Pressures
Fuel
Natural Gas
LP Gas
Gas Supply
Min - Max
Min - Max
Inlet Pressure Tap
(A)
5” - 10.5” WC
(1.25 - 2.62 kPa)
11” - 14” WC
(2.74 - 3.48 kPa)
Manifold Pressure
Fuel
Natural Gas
LP Gas
Gas Supply
Low - High
Low - High
Manifold Pressure
Tap (B)
1.6” - 3.5” WC
(.4 - .87 kPa)
6.4” - 11” WC
(1.59 - 2.74 kPa)
BURNER FLAME ADJUSTMENTS
WARNING: To avoid property damage or personal injury, allow ample time to cool before making any
adjustments.
Burner flame appearance and characteristics are affected by altitude, fuel quality, venting configuration, and
other factors. After installation, additional adjustments may be required to achieve optimum flame appearance
and visual aesthetics.
WARNING: VENTURI ADJUSTMENT MUST BE DONE BY A QUALIFIED SERVICE TECHNICIAN.