8 multi-speeds are available with the combinations of the 3 terminals.
Fig.8-30: Given by multi-speed
X3
X2
X1
Command frequency
Corresponding frequency
and Acc. / Dec. time parameter
OFF OFF OFF
Multi-speed frequency 0
[b1.04], [E2.35]
OFF OFF
ON
Multi-speed frequency 1
[E2.10], [E2.37]
OFF
ON
OFF
Multi-speed frequency 2
[E2.11], [E2.39]
OFF
ON
ON
Multi-speed frequency 3
[E2.12], [E2.41]
ON
OFF OFF
Multi-speed frequency 4
[E2.13], [E2.43]
ON
OFF
ON
Multi-speed frequency 5
[E2.14], [E2.45]
ON
ON
OFF
Multi-speed frequency 6
[E2.15], [E2.47]
ON
ON
ON
Multi-speed frequency 7
[E2.16], [E2.49]
Fig.8-2: Multi-speed terminal settings
● 4: Reserved
● 5: Acceleration / deceleration time terminal 1
● 6: Acceleration / deceleration time terminal 2
4 options of acceleration / deceleration time are available with the combinations of the
2 terminals, as shown in the table below.