Function
code
Name
Setting range
Min.
unit
Factory
default Attribute
b0.02
Access authority
setting
0: Basic parameters
1: Standard parameters
2: Extended parameters
3: Advanced parameters
4: Start-up mode
1
0
RUN/
STOP
b0.03 Reserved
–
–
–
–
b0.04 Reserved
–
–
–
–
System configuration
Function
code
Name
Setting range
Min.
unit
Factory
default Attribute
b0.05 Parameter
initialization
0: No action
1: Restore factory default
2: Remove error record
Note: The value is automatically
set to be 0 after the operation.
1
0
STOP
b0.06 Parameter
replication
0: No action
1: Read parameter
2: Write parameter
Note: The value is automatically
set to be 0 after the operation.
1
0
STOP
b0.07
~
b0.19
Reserved
–
–
–
–
Frequency Converter configuration
Function
code
Name
Setting range
Min.
unit
Factory
default
Attribute
b0.20 Frequency converter
rated voltage setting
200 V: 200 ~ 240 V
400 V: 380 ~ 480 V
1 V
220 V
380 V
STOP
b0.21 Carrier frequency
1 ~ 15 kHz
1 kHz
4 kHz
RUN/STOP
Bosch Rexroth AG
Appendix
DOK-RCON03-EFC-3600***-IT01-EN-P
Rexroth Frequency Converter EFC 3600
196/235