● The default value of [S0.32] and [S0.33] can satisfy most applications, if
slight modification is needed, please try to increase Proportion factor
first to make sure there is no oscillation, then decrease Integrating time
to make sure fast responding and no overshooting.
● [E4.03] “Stall overcurrent prevention level” should be smaller than
[S0.31] “Automatic current limitation level”, otherwise warning "PrSE"
will be displayed and parameter will not be changed.
8.4
Group S2: Motor and Encoder Parameters
S2.00
Rated motor frequency
Setting range
5.00 ~ 400.00 Hz
Minimum unit
0.01 Hz
Factory default 50.00 Hz
S2.01
Rated motor rotation speed
Setting range
1 ~ 30000 rpm
Minimum unit
1 rpm
Factory default Depends on model
S2.02
Rated motor power
Setting range
0.1 ~ 1000.0 kW
Minimum unit
0.1 kW
Factory default Depends on model
S2.03
Rated motor voltage
Setting range
0 ~ 480 V
Minimum unit
1 V
Factory default Depends on model
S2.04
Rated motor current
Setting range
0.01 ~ 655.00 A
Minimum unit
0.01 A
Factory default Depends on model
S2.05
Power-factor
Setting range
0.50 ~ 0.95
Minimum unit
0.01
Factory default Depends on model
S2.10
Stator resistance
Setting range
0.00 ~ 50.00 Ω
Minimum unit
0.01 Ω
Bosch Rexroth AG
Parameter Settings
DOK-RCON03-EFC-3600***-IT01-EN-P
Rexroth Frequency Converter EFC 3600
82/235