5.9.2
Recommendation on Cable Dimensioning
1. Depends on the power of a frequency converter.
2. In table column “Nominal Current of Fuse [A]”, read corresponding information for
fuse.
1. The cable dimensions for inputs and outputs are based on supply
voltages of 1P 200 VAC / 3P 380 VAC.
2. For torque information, see the table below.
Power [kW]
Input side
Output
side
Screw torque
for power
cable terminals
[Nm / lb-in]
(screw size)
PE
Nominal current
of Fuse [A]
Cable size [mm
2
/ AWG]
Cable size [mm
2
/ AWG]
Cable size [mm
2
/ AWG]
Torque
[Nm / lb-in] (screw size)
1-phase 200 VAC class
0.4
10
2.0 / 14
2.0 / 14
0.8 / 7 (M3)
6 / 8
0.8 / 7 (M3)
0.75
16
2.0 / 14
2.0 / 14
0.8 / 7 (M3)
6 / 8
0.8 / 7 (M3)
1.5
20
2.0 / 14
2.0 / 14
0.8 / 7 (M3)
6 / 8
0.8 / 7 (M3)
2.2
25
3.5 / 12
3.5 / 12
1.2 / 10 (M4)
6 / 8
1.2 / 10 (M4)
3-phase 400 VAC class
0.4
6
2.0 / 14
2.0 / 14
0.8 / 7 (M3)
6 / 8
0.8 / 7 (M3)
0.75
10
2.0 / 14
2.0 / 14
0.8 / 7 (M3)
6 / 8
0.8 / 7 (M3)
1.5
10
2.0 / 14
2.0 / 14
0.8 / 7 (M3)
6 / 8
0.8 / 7 (M3)
2.2
16
2.0 / 14
2.0 / 14
1.2 / 10 (M4)
6 / 8
1.2 / 10 (M4)
4.0
20
2.0 / 14
2.0 / 14
1.2 / 10 (M4)
6 / 8
1.2 / 10 (M4)
Fig.5-3: Fuse and cable dimensions
DOK-RCON03-EFC-3600***-IT01-EN-P
Rexroth Frequency Converter EFC 3600
Bosch Rexroth AG
Mounting and Installation
35/235
Summary of Contents for Rexroth EFC 3600
Page 6: ...Bosch Rexroth AG DOK RCON03 EFC 3600 IT01 EN P Rexroth Frequency Converter EFC 3600 IV 235 ...
Page 232: ...230 235 ...
Page 236: ...Bosch Rexroth AG DOK RCON03 EFC 3600 IT01 EN P Rexroth Frequency Converter EFC 3600 234 235 ...
Page 237: ...Notes DOK RCON03 EFC 3600 IT01 EN P Rexroth Frequency Converter EFC 3600 Bosch Rexroth AG ...