● Limit value for 1
st
environment is also relevant, if source of interference
of 2
nd
environment affects 1
st
environment.
● Designations “class” and “group” according to CISPR 11.
● QP: measuring method quasi peak measurement.
● AV: measuring method arithmetic averaging.
Second Environment, Industrial Area
Facilities not directly connected to a low-voltage mains to supply buildings in residential
areas.
If the limit values in an industrial area separated from public supply by a transformer
station only have to be complied with at the property boundary or in the neighboring
low-voltage mains, the filter might not be necessary. In the vicinity such as measuring
sensors, measuring lines or measuring devices, it is normally required to use the
interference suppression filter.
Increasing the noise immunity of a sensitive device can often be the economically
better solution compared to measures of interference suppression at the drive system
of installation.
First Environment
Environment containing residential areas and facilities directly connected, without
interstage transformer, to a low-voltage mains supplying buildings in residential areas.
Medium-sized manufacturing plants and industrial establishments can be connected to
the public low-voltage mains together with residential buildings. In this case there is a
high risk for radio and television reception if there are not any measures for radio
interference suppression taken. Therefore, the indicated measures are generally
recommended.
Nominal Current of Supply Mains
The nominal current of the supply mains (> 100 A or ≤100 A) is specified by the local
power supply company at the connection point of the mains. For industrial companies,
for example, such connection points are the interconnecting stations from the power
supply company.
Since it is impossible to obtain the lower limit values for residential areas with all
applications by means of usual measures (like in the case of large and electrically not
closed installations, longer motor cables or a large number of drives), the following note
included in EN 61800-3 has to be observed.
DOK-RCON03-EFC-3600***-IT01-EN-P
Rexroth Frequency Converter EFC 3600
Bosch Rexroth AG
Electromagnetic Compatibility (EMC)
153/235
Summary of Contents for Rexroth EFC 3600
Page 6: ...Bosch Rexroth AG DOK RCON03 EFC 3600 IT01 EN P Rexroth Frequency Converter EFC 3600 IV 235 ...
Page 232: ...230 235 ...
Page 236: ...Bosch Rexroth AG DOK RCON03 EFC 3600 IT01 EN P Rexroth Frequency Converter EFC 3600 234 235 ...
Page 237: ...Notes DOK RCON03 EFC 3600 IT01 EN P Rexroth Frequency Converter EFC 3600 Bosch Rexroth AG ...