CRC higher byte
DAH
End
Transmission time for 3.5 bytes
Fig.13-18: Function 0x10_Request from RTU master
Start
Transmission time for 3.5 bytes
Slave address
01H
ModBus function code
10H
Higher byte of write register start address 01H
Lower byte of write register start address 14H
Higher byte of register number
00H
Lower byte of register number
02H
CRC lower byte
00H
CRC higher byte
30H
End
Transmission time for 3.5 bytes
Fig.13-19: Function 0x10_Response from RTU slave
● Function 0x17: Read/Write N register words, range 1 ~ 16.
Example: To read data in 2 continuous registers starting from address 0114H, write
00C8H and 00C8H to 2 continuous registers starting from address 0117H. The
frame structure is described in the tables below:
Start
Transmission time for 3.5 bytes
Slave address
01H
ModBus function code
17H
Higher byte of read register start address 01H
Lower byte of read register start address
14H
Higher byte of read register number
00H
Lower byte of read register number
02H
Higher byte of write register start address 01H
Lower byte of write register start address 17H
Higher byte of write register number
00H
Lower byte of write register number
02H
Bytes of data for writing
04H
Higher byte of data in register 0109H
00H
Lower byte of data in register 0109H
C8H
Higher byte of data in register 010AH
00H
Lower byte of data in register 010AH
C8H
DOK-RCON03-EFC-3600***-IT01-EN-P
Rexroth Frequency Converter EFC 3600
Bosch Rexroth AG
Communication Protocols
179/235