Fig.8-33: Characteristics curve 2
8.7
Group E1: Output Terminal Parameters
E1.00
OC outputs
Setting range
0 ~ 17
Minimum unit
1
Factory default 1
E1.02
Relay outputs
Setting range
0 ~ 17
Minimum unit
1
Factory default 1
● 0: Frequency converter ready for running
After powering on, if no error happens and there is no run command, output active
indicates that the frequency converter is ready for running.
● 1: Frequency converter is running
The terminal outputs indicating signal when the frequency converter is running and
has frequency output (including 0.00 Hz).
● 2: DC braking indication
When the frequency converter is in the starting or stopping DC braking, output is ac‐
tive.
● 3: Frequency converter running at zero speed
When the frequency converter is running with zero speed, output is active.
During dead zone time of rotation direction change, there is no output for
this selection.
● 4: Frequency / speed arrival signal
Bosch Rexroth AG
Parameter Settings
DOK-RCON03-EFC-3600***-IT01-EN-P
Rexroth Frequency Converter EFC 3600
100/235