b1.11
Operating panel controls direction
Setting range
0 ~ 1
Minimum unit
1
Factory default 0
This parameter is only applicable for operations via the operating panel.
● 0: Forward rotation
● 1: Reverse rotation
The relationship between [b1.10] and [b1.11] is:
Fig.8-3: Relationship between [b1.10] and [b1.11]
Direction control [b1.10]
Default direction [b1.11]
Final direction
0
Both directions
Forward
Forward
Reverse
Reverse
1
Forward only
Forward
Forward
Reverse
STOP with error
2
Reverse only
Forward
STOP with error
Reverse
Reverse
3
Inverse default direction
Forward
Reverse
Reverse
Forward
For "STOP with error", please see
chapter 9.5 "Diagnosis on Errors" on
page 128
.
Normally, each RUN / STOP command source has its own direction command source.
The generated direction is further controlled by internal direction control ([b1.10]).
Frequency source
RUN / STOP command
source
Direction command source
Multi-speed
Operating panel
Defined by multi-speed / PLC
configuration
2-wire / 3-wire running control
[E0.00]
2-wire / 3-wire running control
[E0.00]
Communication
Communication
DOK-RCON03-EFC-3600***-IT01-EN-P
Rexroth Frequency Converter EFC 3600
Bosch Rexroth AG
Parameter Settings
63/235
Summary of Contents for Rexroth EFC 3600
Page 6: ...Bosch Rexroth AG DOK RCON03 EFC 3600 IT01 EN P Rexroth Frequency Converter EFC 3600 IV 235 ...
Page 232: ...230 235 ...
Page 236: ...Bosch Rexroth AG DOK RCON03 EFC 3600 IT01 EN P Rexroth Frequency Converter EFC 3600 234 235 ...
Page 237: ...Notes DOK RCON03 EFC 3600 IT01 EN P Rexroth Frequency Converter EFC 3600 Bosch Rexroth AG ...