Table 32: Specifications.
Temperature
Storage and Operating Temperature: +32°F to +120°F (0°C to +49°C)
Power
Input Power: 220 V 50 Hz or 120 V, 60 Hz, 2.2 A
Notification Appliance Circuit (NAC) Power: Each NAC has 24 VDC nominal, unfiltered
power with up to 2.5 A capacity (but limited by overall 4.0 A capacity). Refer to
FPD-7024
NAC Compatibility List
(P/N: F01U010791) for compatible NAC devices.
Auxiliary Power: 24 VDC nominal, unfiltered, 1.0 A
Initiating Circuit (Smoke) Power: 24 VDC nominal, filtered, 1.0 A. Refer to
FPD-7024 Fire
Alarm Control Panels
(P/N: F01U010790) for compatible smoke detection devices.
Option Bus Power: 12 VDC nominal, 500 mA Optional Standby Batteries: Two 12 V (in
series), 7 to 40 Ah
Notification Appliance
Circuits (NACs)
Two on-board notification circuits NAC 1 and NAC 2. These are 24 V outputs for
notification devices with up to 2.5 A capacity (but limited by overall 4.0 A capacity) on each
circuit.
Wire for standard Class B, Style Y or Class A, Style Z as needed.
Configurable for patterns: steady, pulsing, California March, ANSI code 3, synchronized
Wheelock, synchronized Gentex, and synchronized System Sensor.
Local Relays: The main control panel includes Three Form “C” relays. The relay contacts
are rated at 5 A, 28 VDC. No over existing limiting is performed on the contacts of these
relays. The default selection for the relays is to indicate general alarm and general system
trouble and supervisory. By using point or zone mapping, they can be programmed to
activate in a wide variety of conditions.
When a local relay is programmed for trouble it is energized in the normal state.
This causes the common and normally-open terminals to be shorted when not
in the trouble condition.
Relays
D7035 Remote Relay Module: The D7035 is an octal relay module that provides eight
Form C relay outputs. It connects to the FPD-7024 through the option bus. The outputs are
fully programmable, exactly as the local relays are programmed. Each output operates
independently of the other seven to provide complete flexibility. Communication with the
D7035 is supervised.
Contact Rating: 5 A @ 28 VDC
Number of Modules: two units maximum
Wiring Requirements: Refer to
Section 2.2, Option Bus Wiring Requirements
on page 19.