FPD-7024
|
Operation and Installation Guide | 3.0
System Operation
.
Bosch Security Systems, Inc. | 1/10 | F01U008458-03
29
Figure 10: Mapping, Inputs, Zones, and Outputs
General Alarm Zone 63 drives LR 2.
Input Point 1 is assigned to Zone 1, mapped to NAC Point 1.
Input Point 2 is assigned to Zone 2, mapped to NACs 1 and 2.
Input Point 3 is assigned to Zone 2, mapped to NACs 1 and 2.
Input Point 4 is assigned to Zone 2, mapped to NACs 1 and 2.
Input Point 5 is assigned to Zone 3, mapped to NAC 2, LR 1 and RR 1.
LR:
Local relay
RR:
Remote relay
Up to 64 zones can be assigned. The installer can assign Zones 1 to 50. Zones 51 to 63 are hard-coded to
pre-assigned conditions. Refer to
Table 13.
Table 13: Pre-Assigned Zones
Zone Pre-Assigned
Condition
51
Reserved for future use.
52
General Fire Alarm, Waterflow (non-silenceable). Same as Zone 53, but remains active even while system is silenced.
53
General Fire Alarm (silenceable). Active when a fire alarm condition is present; does not activate for waterflow.
54
Activates for approximately 7 sec before dialing, to initiate dial tone on a ground start phone system.
55
General Supervisory (silenceable)
56
General Waterflow (silenceable)
57
Communication Trouble. Active when the dialer fails to communicate; remains active until communication through the
digital communicator is restored.
58
General Supervisory Alarm (non-silenceable). Active when any supervisory alarm condition is present.
59
Alarm Verification. Active while alarm verification is in progress. This starts with the first detection of an alarm to be
verified and clears in two minutes, or when system is reset.
60
No AC. Active when AC power fails.
61
General Waterflow (Non-silenceable). Active when any waterflow alarm is present.
62
General Trouble. Active while any system trouble is present, not active in test and programming modes.
63
General Alarm, Waterflow (non-silenceable). Active while any alarm, including supervisory, is present. Remains active
even while system is silenced.