FPD-7024
|
Operation and Installation Guide | 5.0
Control Panel Programming
76
Bosch Security Systems, Inc. | 1/10 | F01U008458-03
NEW DEVICE @ xxx
2 – SINGLE INPUT
3 – I/O MODULE
4 – MUX SMOKE
5 – SMOKE W/FRZ
6 - DUAL INPUT
7 - OCTAL INPUT
0 – NO DEVICE
Use this menu to define the device type. Press the number key that corresponds with the device type
installed at the address. If a detected device should not be installed and should be left inactive, press [0/Prog]
to bypass the new device.
Ensure that the correct device type is selected for each point. Incorrectly specified device types
can cause multiplex devices to malfunction or fail to operate.
All inputs are configured to use Point Function 10 as they are added. Points added during auto programming
are configured for the following operation:
Point Function 10 (Fire Alarm, Fast Response, Non-silenceable, Not Local-only)
Open Status = Trouble
Output Zone 9
Alarm Verify = NO
Latching = YES
The programming of input points can be changed when auto programming completes using the input-
programming menu.
When I/O modules are added during auto programming, the relay (second point) is configured to activate on
any alarm, non-silenceable (Zone 63). This can be changed when auto programming completes by using the
output-programming menu.
The FPD-7024 performs some basic error checks when new devices are added. The following errors can be
shown during the process of adding a device:
ADDRESS ERROR #
AT ADDRESS xxx
In the previous message, # is replaced by a code number and xxx is replaced by the affected address that
indicates the type of error. Refer to
Table 26
for code numbers and corresponding error message
descriptions.
Table 26: Auto Programming Error Messages
Code Error
Description
1
New point is under an existing point
The new point is in the space required for an existing multi-
address device. This is checked when auto programming
first starts.
2
Point overlaps existing point
There are already devices configured at one of the
addresses required for the new multi-point device.
3
Point is at an illegal address
The addresses at which multi-address devices can be
installed are restricted. Refer to
Table 9
on page 15 or the
specific device’s installation instructions for details.
4
Too many multiplex relays
Only 20 input output devices can be supported on a given
bus.