FPD-7024
|
Operation and Installation Guide | 5.0
Control Panel Programming
.
Bosch Security Systems, Inc. | 1/10 | F01U008458-03
75
If no errors are found, the FPD-7024 starts a scanning process that takes approximately one minute to
complete, while showing the following display:
AUTO PROGRAM
SCANNING
PLEASE WAIT...
When the scanning is completed, the FPD-7024 checks for missing devices. Missing devices are addresses
with no devices on the multiplex buses, but are programmed into the FPD-7024’s site-specific memory area.
If missing devices are detected, the FPD-7024 shows the following menu (where xxx is the address of the
first point of the missing device):
MISSING PT @ xxx
0-
DELETE POINT
1-
KEEP POINT
2-
DEL REMAIN
3-
KEEP REMAIN
DELETE POINT:
If selected, the missing point and any addresses it implemented (up to eight for an octal
input module) are permanently deleted from the site specific memory area. If the deleted device is an I/O
module, the output zones that were programmed for the relay are reset to 0. If additional devices are found to
be missing, the above display is repeated for each missing device.
KEEP POINT:
If selected, the FPD-7024 retains the programming for the existing point and continues
scanning for additional missing points.
DEL REMAIN:
If selected, the following prompt # KEY TO CONFIRM appears at the FPD-7024. If the
[#/Enter]
key is pressed, all the missing points are deleted from the site-specific memory area and the auto
program process continues with the DEVICES FOUND menu. If any other key is pressed, the existing point is
kept and the control panel continues scanning for additional missing devices.
KEEP REMAIN:
If selected, no additional points are deleted and the auto program process continues with the
DEVICES FOUND menu. Points individually deleted with the DELETE POINT command before selecting the
KEEP REMAIN command stay deleted when KEEP REMAIN is selected.
Use the DEL REMAINING feature with caution. Any devices missing from the multiplex buses
during the DEL REMAINING operation, even momentarily, are permanently deleted. These points
do not operate, and do not generate trouble conditions even if they are returned to the bus.
When the delete point operation is finished, the FPD-7024 shows for five seconds the total number of points
that were deleted from the control panel (xxx indicates the number of points that were removed from the
control panel’s site specific configuration).
AUTO PROGRAM
xxx POINTS DELETED
Confirm that only the expected number of points was removed from the system. Points that are removed from
the control panel’s site-specific configuration do not operate and are not supervised even if they are returned
to the bus.
When the point delete process completes, the auto programming process automatically checks for new
devices on the buses. New devices are found when a device is present on one of the multiplex buses, but its
address is not programmed into the control panel’s site-specific memory. If new devices are detected, the
FPD-7024 shows the following menu (where xxx is the address of the first new device found):