FPD-7024
|
Operation and Installation Guide | 5.0
Control Panel Programming
.
Bosch Security Systems, Inc. | 1/10 | F01U008458-03
53
5.5 PROG
OUTPUTS
PROG OUTPUTS
1-
NACs
2-
RELAYS
5.5.1 Programming
NACs
Shortcut: 0-
PROG
,
5-
PROG OUTPUTS
,
1-
NACs
The main control panel includes two local NACs (NAC 1 and NAC 2). The FPD-7024 can also support up to
four FPP-RNAC-8A-4C Remote NAC Power Supplies, which offers a total of 16 remote NACs (four NACs per
RNAC).
The following window appears:
NAC OUTPUTS
1-
LOCAL
2-
REMOTE 1
3-
REMOTE 2
4-
REMOTE 3
5-
REMOTE 4
Press the number key that corresponds to your selection.
Local NACs
Shortcut: 0-
PROG
,
5-
PROG OUTPUTS
,
1-
NACs
The display scrolls through the NAC options. Press [1] for LOCAL.
The following window appears:
ONBOARD NAC
1-
NAC #1
2-
NAC #2
Press the number key that corresponds to your selection.
The display scrolls through the following selection:
PROG NAC
1-
(reserved)
2-
CONFIGRATION
3-
ZONE ASSIGNS
Press the number key that corresponds to your selection.
If you select [2] from the PROG NACs menu, the following selections scroll:
NAC CONFIG ( )
1-
STEADY
2-
PULSING
3-
CALIFORNIA MARCH
4-
TEMPORAL
5-
WHEELOCK
6-
GENTEX
7-
SYSTEM SENSOR
For more
NAC CONFIG
parameter information, refer to
Table 15
on page 32.
These selections control the pattern (code) for the selected NAC. Press the number key that corresponds
with the desired pattern:
•
Steady:
Output turns on and stays on while the NAC is active.
•
Pulsing:
Output turns on for 0.5 sec and off for 0.5 sec.
•
California March:
Output turns on for 0.25 sec and off for 0.25 sec.