FPD-7024
|
Operation and Installation Guide | 5.0
Control Panel Programming
.
Bosch Security Systems, Inc. | 1/10 | F01U008458-03
77
When the point adding operation completes, the FPD-7024 shows for five seconds the total number of points
that were added to the control panel. Confirm that the number of devices added matches the expected
number.
AUTO PROGRAM
xxx POINTS ADDED
If a new device is not detected on the bus during the point adding operation, the device does not
operate and does not generate trouble conditions even if it remains connected to the bus.
When the point adding operation completes, the display shows the total number of points on the system
(xxx is the total number of points, not devices).
AUTO PROGRAM
xxx MUX POINT
Confirm that the system shows the exact number of points expected. Points that are not included in the total
count do not operate and do not generate trouble conditions.
After the count of total points appears for approximately 10 sec, the FPD-7024 restores the multiplex system
to normal operation. This process takes approximately 50 sec and the following message appears during the
restoral process:
AUTO PROGRAM
RESTORING
PLEASE WAIT...
As with any programming change to a system, test the system for proper operation before
returning it to service. At least test each added multiplex point after auto programming completes.
Test according to NFPA 72.
5.9.5 Removing MUX Devices
Shortcut: 0-
PROG
,
9-
PROGRAM MUX
1
- MUX EDIT
To remove a previously programmed multiplex device, use the MUX Edit feature.
PROGRAM MUX
1-
MUX EDIT
2-
MUX PROGRAM
3-
BUS TYPE
4-
AUTO PROGRAM
From the Program MUX menu, press [1] to select MUX Edit.
The following window appears:
DEVICE TYPE (__)
0- NO DEVICE
2- SINGLE INPUT
3- I/O MODULE
4- MUX SMOKE
5- SMOKE W/FRZ
6- DUAL INPUT
7- OCTAL INPUT
Description..................... Model
0- NO DEVICE
2- SINGLE INPUT ........ D7044/M, D7045, FMM-7045,
D7052(Class A)
3- I/O MODULE ............ D7053
4- MUX SMOKE ........... D7050, D7050TH, D343
5- SMOKE W/FRZ ....... Not Used
6- DUAL INPUT ............ D7052(Class B)
7- OCTAL INPUT.......... D7042
Press [0/Prog] for No Device. Then enter the address for the point you wish to delete.