
FPD-7024
|
Operation and Installation Guide | 5.0
Control Panel Programming
.
Bosch Security Systems, Inc. | 1/10 | F01U008458-03
57
Table 21: Pre-Assigned Zone Quick Reference
Zone Pre-Assigned
Condition
52
General Fire Alarm (non-silencing)
53
General Fire Alarm, (silencing)
54
Ground Start
55
General Supervisory, (silencing)
56
General Waterflow, (silencing)
57 Communication
Trouble
58
General Supervisory Alarm (non-silencing)
59 Alarm
Verification
60
AC Failed
61
General Waterflow Alarm (non-silencing)
62
General Trouble
63
General Alarm, Waterflow Supervisory (non-silencing)
An output point cannot be assigned to more than four zones. Each output does not need to be assigned to
four zones. Each zone can have any number of outputs assigned to it.
Multiplex Relays
Shortcut: 0-
PROG
,
5-
PROG OUTPUTS
,
2-
RELAYS
Do not use this menu to program addresses configured as inputs.
The display scrolls through the Relay options. Press [4/ ] for MULTIPLEX. The following window appears:
MUX OUTPUT
(009 - 255):
Enter the number corresponding with the output to be programmed and press [#/Enter]. The output number of
a multiplex relay is the second point of an I/O module. Adding 1 to the address of the I/O module gives the
address of the relay in the module. When the relay is selected, the display asks you to enter four zones to
activate this output:
OUTPUT ZONE A:
(00 - 63):
Enter the first zone (00 to 63) you want to assign to this output and press [#/Enter]. A similar display for Zone
B, C and D appears, allowing up to four zones be assigned to this input. When all four zones are assigned,
the previous window appears.
An output point cannot be assigned to more than four zones. Each output does not need to be assigned to
four zones. Each zone can have any number of outputs assigned to it.