FPD-7024
|
Operation and Installation Guide | 5.0
Control Panel Programming
.
Bosch Security Systems, Inc. | 1/10 | F01U008458-03
43
Enter the user for whom you want to program the authority level and press [#/Enter]. The following window
appears and scrolls through the following choices:
USER 1 ATHRY ( )
0-
NONE
1-
MAXIMUM
2-
MEDIUM
3-
MINIMUM
Press the number key that corresponds to your selection. The existing setting is shown in parentheses on the
first line. After you have programmed the user authority, the previous window appears.
5.3 PROG
SYSTEM
PROG SYSTEM
1 - (reserved)
2 - TIMERS
3 - AC LINE SYNC
4 - OPTION BUS
5 - PIN REQURED?
6 - (reserved)
7 - REMOTE PGM
5.3.1 Program
Timers
Shortcut: 0-
PROG
,
3-
PROG SYSTEM
,
2-
TIMERS
The following window appears:
TIMERS
1-
SMOKE RESET
2-
AC FAIL DLY
3-
AUTO SILENCE
4-
(reserved)
5-
DISPLAY RATE
Smoke Reset
Shortcut: 0-
PROG
,
3-
PROG SYSTEM
,
2-
TIMERS
This feature determines how long the smoke detector power is off after reset. No alarms are registered by the
system for 5 seconds after power is returned.
The display scrolls through the TIMERS options. Press [1] for Smoke Reset. The following window appears:
SMOKE RESET (__)
(1-16 SECS): __
Enter the time and press [#/Enter]. The existing setting is shown in parentheses on the first line. After you
have programmed the smoke reset, the previous window appears.
AC Fail Delay
Shortcut: 0-
PROG
,
3-
PROG SYSTEM
,
2-
TIMERS
This feature sets the number of hours the control panel waits after an AC failure before sending an AC Failure
report. A setting of DC causes the system to send a report when 25% of the battery capacity is used.