FPD-7024
|
Operation and Installation Guide | 5.0
Control Panel Programming
.
Bosch Security Systems, Inc. | 1/10 | F01U008458-03
41
Press [1] to select Test Time. The following window appears:
AUTO TEST TIME
HHMM:________
Enter the time followed by the [#/Enter] key.
Test Frequency
Shortcut: 0-
PROG
,
1-
PROG TIME
,
2-
AUTO TEST
This feature allows you to program how often the automatic test reports are sent. The first test is sent when
the programmed test time matches the system time. Subsequent reports are sent according to the selected
interval.
The following window appears:
AUTOMATIC TEST
1-
TEST TIME
2-
TEST FREQNCY
Press [2/
▲
] to select Test Frequency. The following window appears:
AUTO FRQNCY (__)
1-
4 HOURS
2-
12 HOURS
3-
24 HOURS
4-
7 DAYS*
5-
28 DAYS*
* Refer to
Table 15
on page 32.
Press the number key that corresponds to your selection. The existing setting is displayed in parentheses on
the first line. After you have programmed the test frequency, the previous window appears.
5.1.3 Daylight Saving Time
Shortcut: 0-
PROG
,
1-
PROG TIME
,
3-
DAYLIGHT SAV
This feature enables automatic adjustment of system time for Daylight Saving Time. The dates for the
adjustment are pre-programmed in the system.
The following window appears:
DAYLIGHT SAV
1-
DISABLE
2-
ENABLE
Press [1] to select DISABLE or to select [2/
▲
] to ENABLE. After you have programmed this feature, the
previous window appears.
5.2 SECURITY
SECURITY
1-
PINS
2-
AUTHORITY
5.2.1 Personal Identification Numbers (PIN)
Programmer PIN
Shortcut: 0-
PROG
,
2-
SECURITY
,
1-
PINS
The Programmer PIN is the code used by the installer to configure and operate the panel. Factory default
code is
9876
and may be changed at any time.