FPD-7024
|
Operation and Installation Guide | 5.0
Control Panel Programming
.
Bosch Security Systems, Inc. | 1/10 | F01U008458-03
69
4/2 RPT CODS
0-
SYSTM IN TST
1-
SYS TEST RST
2-
SILENCE
3-
FIRE DRILL
4-
FIRE DRL RST
5-
OPEN RST RPT
6-
LOW BATTERY
7-
LOW BATT RST
8-
AC FAILURE
9-
MORE
Pressing [9] allows programming additional reports:
4/2 RPT CODS
0-
AC FAIL RST
1-
TEST REPORT
2-
OFF NORM TEST
3-
PHONE 1 TRBL
4-
PN 1 TRB RST
5-
PHONE 2 TRBL
6-
PN 2 TRB RST
7-
SYSTEM TROUB
8-
SYS TRB RST
Pressing [9] returns you to the previous group of reporting codes.
Press the number key that corresponds to your code selection. A window based on your previous selection
allowing entry of two hex digits appears:
SYSTM IN TST ( )
0 THRU 9
<HISTORY>: A
<TEST>: B
<DISABLE>: C
<DRILL>: D
<SILENCE>: E
<RESET>: F
Enter digits that correspond to the selected condition by pressing a number key, or one of the special keys if a
hex character is needed. Press [#/Enter] and the previous display appears.
5.7.3 BFSK Report Codes
When BFSK reporting is used, most reporting codes are fixed and do not need programming. There are five
reports that the control panel can send that are not standard BFSK codes:
•
Off normal at test: Sent if the panel is off-normal at the automatic test time.
•
Open reset report: Sent when the reset key is pressed.
•
Silence: Sent when the silence key is pressed.
•
Fire drill, fire drill restore: Sent for fire drill operations.