70
BONMET motion GmbH/www.bonmet.com/www.bonmet.de
Value
Frame type
0
8 bit, no parity bit, 2 stop bit
1
8 bit, odd parity bit, 2 stop bit
2
8 bit, even parity bit, 2 stop bit
Pn-188
Parameter
CANOpen node ID
Modbus address
-
Unit
-
Range
1
~
127
Default
1
CANbus object
-
Attrib
R/W
(
NOT SUPPORT
)
Pn-189
Parameter
CANOpen baudrate
Modbus address
-
Unit
-
Range
0
~
5
Default
5
CANbus object
-
Attrib
R/W
(
NOT SUPPORT
)
R-1
Parameter
Index reset clear
Modbus address
0x1C51
Unit
-
Range
-
Default
-
CANbus object
0x2C51.0
Attrib
WC
Control mode
:
All
Details
:
This parameter is used to Clear the current index reset status, and start to search index;
Value
Function
0x01
Clear the current index reset status
Others
No effects
R-2
Parameter
Operation command for EEPROM
Modbus address
0x1C53
Unit
-
Range
-
Default
-
CANbus object
0x2C53.0
Attrib
WC
Control mode
:
All
Details
:
This parameter is used to adjust EEPROM,when dealing with user parameters.
Value
Function
0
Termination current EEPROM operation
1
Read the data from EEPROM
2
Read the data from the backup area of EEPROM
3
Write the data into EEPROM
4
Write the data into the backup area of EEPROM
5
Restore default value
R-3
Parameter
Modbus synchronous command selection
Modbus address
0x1C27
Unit
-
Range
0~2
Default
0
CANbus object
-
Attrib
R/W
Control mode
:
All
Details
:
This parameter is used to select the synchronous command selection for position/speed/torque control mode.
Value
Function
0
Synchronous command invalid
,
drive would receive command through
traditional I/O mode only.
1
Manufacturer parameter, doesn‘t open to customers.