103
3.4.2
If necessary, during on-receipt inspection, a full functional check can be carried out. The
full verification method is described in 3.4.2.1 - 3.4.2.22.
3.4.3
A complete check of the product's performance during the on-receipt inspection is
carried out by persons who read carefully this manual, understand the principle of the product's operation,
and have an electrical Safety Qualification of Class II, at least.
3.4.4
The check is carried out under normal climatic conditions in accordance with GOST
15150-69:
–
ambient temperature - (25 ± 10) ° С;
–
relative air humidity - (45 - 80) %;
–
atmospheric pressure - (630 - 800) mmHg. (84 - 106.7) kPa.
3.4.5
The check is performed with the default configuration settings of the products.
3.4.6
The time for checking the technical condition of one product does not exceed 10
minutes (excluding the connection time).
3.4.7
The wiring diagram of the product when carrying out a complete functional check is
shown in Figure 3.4.1
. . .
+
+
Rб
HL
Rб
HL
Rб
HL
К4
+
+
+
+
А
+
0V
-
ШС1
ШС2
ШС19
7
ШС20
9
1
7
9
Rок
11
13
Rок
6
. . .
ХТ4
-
+
-
20 шт.
К1
К2
-
Rб
HL
К3
К5
-
-
. . .
К6
К7
-
-
Rб
HL
0V
PA1
12 ... 24 VDC
Rок
8
3
4
. . .
Rок
10
2
3
6
8
10
ХТ7.1
2
1
12
14
+U1
ХТ7.2
5
4
RS-485-В
RS-485-А
ХТ1
ХТ6.1
-
+
ХТ6.2
4 шт.
2
1
5
4
+U2
3
СИГНАЛ - 20М
Figure 3.4.1. Connection for Complete Functional Check
Where:
–
Rt
- terminal resistor 0.5 W - 4.7 kΩ (MF 1 / 2W-4K7 ± 5% or similar) - 24 pcs., included in
the delivery set;
–
-
Rb
- ballast resistor limiting the LED current. With a supply voltage of 12 V, the resistors Rb
are 1.0 kΩ (for example, MF 1 / 4W-1K ± 5% or similar). With a supply voltage of 24 V, the
nominal resistors Rb are 2.0 kΩ (for example, MF 1 / 4W-2K ± 5% or similar) - 7 pcs .;
–
HL
- LED with a rated current of at least 20 mA (for example GNL-5012HD or similar),
arbitrary color - 7 pcs. ;
–
PA1
- ammeter.
3.4.7.1
Connection and disconnection of the wires for testing purpose shall be curried only
when the product is powered off.
3.4.7.2
The check is carried out in the following sequence.
3.4.7.3
Power on the product. Control the playback of the ‘Awake’ signal.
3.4.7.4
Check the current consumption of the product. It must not exceed that specified in