By commands of the network controller over RS-485 (centralized control).
1.4.3.19
The following shall be done to set local control for Output X:
–
Interlink output with required inputs (
Output X
parameter);
–
Set the
Activation Delay
for Output X for each interlinked input;
–
Select
Output Type
(if necessary);
–
Select
Control Program
);
–
Set an Operation Time (if a program with limited time is used)
–
Define where
START/STOP
buttons are used);
–
Select Monitoring Mode;
–
Define Activated Output Monitoring mode);
–
Define whether output operation(on/off) events are reported (if needed).