31
–
Debounce Time of transition from the
SHORT CIRCUIT
(
OPEN-CIRCUIT
) state to the
ARMED
state is 1 second.
The connection of normally opened and normally closed fire manual station on the Input of Type
16 is described in
1.4.2.13.11.
Type 17: Flood Alarm
This input supports connection of Food detectors.
The input circuit resistance corresponding to physical states are provided in
Possible logical states:
–
FLOOD DETECTOR NORMAL
– flood detector(s) is (are) normal, the input is monitored;
–
DISARMED
- the input is not monitored;
–
DISABLED
- the input is not monitored; the monitoring is disabled by the network
controller;
–
OPEN CIRCUIT
– the input resistance is more than 6 kΩ;
–
FLOODING DETECTED
– activation of flood detector
Algorithm of flood alarm input
Input disablement (transition to the
DISABLED
status) can be done manually only using the
DISABLE command of the network controller (the S2000-M panel ver.4.13 (3.13) or newer).
When enabled in the
DISABLED
status, the input goes to one if the following state:
–
FLOODING DETECTOR NORMAL
–
FLOODING DETECTED
–
DISARMED
If the input monitoring is enabled with the
Never Disarm
parameter applied, the input goes to an
actual state, otherwise the input is disarmed.
The input monitoring can be enabled by the following way:
manually by the ENABLE command of the network controller (S2000M panel v.4.13
(3.13) and higher)
manually by the ARM or ENABLE command of the network controller (S2000M panel
v.4.12 (3.12) and lower)
manually using the Signal-20M controls when operated in combination with the S2000M
control panel v.4.12 (3.12) and lower
manually using the Signal-20M controls in standalone operation
The monitoring of Input 17 can be disabled manually using panel controls or by the DISABLE
command from the network controller. In this case the input goes to the
DISARMED
status and is not
monitored.
The enablement of Input 17 can be down manually using panel controls or by the DISABLE
command from the network controller. In this case the input goes from the
DISARMED
status to the
status corresponding to the input resistance at the moment.