47
If the auxiliary input is restored but, but the output activation condition by other inputs is still in
place:
–
The control programs with unlimited operation time (1,2,5 and 6) are resumed;
–
The control programs with limited operation time (3, 4, 7, 8, 12, 50 – 53) are not resumed;
Thus, the violation of auxiliary input of the Signal-20M suspense running general purpose
programs with unlimited operation time and prohibits general purpose programs with limited operation
time.
1.4.3.25
To enable the output centralized control (be network controller), settings shall be
provided both for the control panel and network controller.
The Signal-20M settings:
–
Select the
0- No Control
program for the
Control Program
–
Select
Monitoring Mode
;
–
Select the activated output monitoring mode (the
Activated Output
);
–
Select Simple for
Output Type
;
–
Select On/Off Event (if on/events reporting is needed).
If you select ‘Control Programs’ - ‘0 - No Control’, centralized control is enabled for the output
regardless of the interlink between the output and input (Output X Control parameter).
When configured in this way, after powering the control panel, the output will be turned off until
the first command from the network controller is received. It may take some time for the network
controller to form a command that switching the output to the state corresponding to the current state of
the sections associated with the output.
Therefore, if a centralized control program is used that assumes the initial state ‘On’ (one of the
programs ‘Turn off ...), it is advisable to switch the output to the ‘On’ state immediately after turning on
the power. This requires:
- select any ‘Control Program’ assuming the initial state ‘On’, for example, ‘2 - Turn off’ (see
););
- unselect all interlinks between the output and all inputs (
Output X
/Control).
To configure the network controller, the following shall be done in the controller configuration:
- set the interlink between the output (relay) and partitions;
- assign a relay control program;
- set the delay and operation time for the relay.
For details, see the User Guide of the respective network controller