6
–
Arming and disarming inputs through its own control tools or by commands from the network
controller;
–
Controls audible and visual alarm devices in the auto mode (local control);
–
Controls audible and visual alarm devices in the manual mode from built-in controls and
remote control devices);
–
Controls fire protection equipment as instructed by the S2000M panel (centralized control);
–
Monitors for power faults and tampering attempts.
WARNING!
The following Bolid-manufactured detectors and devices are recommended for the use with the
Signal-20M:
–
IP 212-31 DIP31 Threshold Photoelectric Smoke Detector
–
IP435-8/101-04-AR1 SOnet combined threshold CO and fixed temperature and rate-of-rise
detector
–
IPR 513-3M Resettable Manual Call Point
–
IPR 513-3M IP 67 Resettable Manual Call Point;
–
UDP 513-3M Manual Release Station
The use of the above devices is guaranteed a complete compatibility with the Signal-20M in
accordance with GOST R 53325-2012.
In addition, the following intrusion detection devices manufactured by Bolid company are
recommended for the operation with the Signal-20M:
–
ECHO-5 Ultrasonic Motion Detector
–
IRBIS ver 01glass break detector
1.1.5
The panel is not scalable system.
1.1.6
The panel supports connection to PC for control and programming functions.
1.1.7
The panel is designed for 24\7
continuous
operation
1.1.8
The panel is a reparable device with periodic maintenance
1.1.9
The Panel is not designed to be used in aggressive, dust, explosive and fire-hazardous
environments.
1.2
Specifications
Table 1.2.1 Specifications
No
Parameter
Value
1.2.1
DC supply voltage, V
10.2 … 28.0
1.2.2
Consumption current, mA, no more *
- in quiescent mode
- in the FIRE mode
* excluding current consumption of alarm devices
400
650
1.2.3
Power inputs
2
1.2.4
Startup time, s
5
1.2.5
Inputs
20
1.2.6
Voltage on unloaded input terminals, V
26.5 … 27.5
1.2.7
Input short-circuit current limitation, not more than, mA
26,5
1.2.8
Resistance of input terminal resistor, kΩ
4.7±5 %
1.2.9
Max. current consumption of all detectors in quiescent mode, mA
- type 1 (Fire smoke) inputs
- type 2 (Fire combined) inputs
3,0
1,2