If incorrectly connected the antifreeze thermostat will not operate and the evaporator may freeze.
On all units the hydraulic connections are made by flexible joints and welding pipe.
EVAPORATOR WATER
The water inlet and outlet must be connected in the positions indicated
as labelled on the unit.
4.4 EVAPORATOR WATER PIPE CONNECTIONS
A constant water flow to the evaporator must be guaranteed at all
operating conditions to prevent liquid refrigerant from entering the
compressor and causing irreparable damage.
Compressors start and stop often due to changes in cooling demand. In hydraulic circuits with low water volume,
where the thermal inertia action is low, it is advisable to verify that the water volume equals or exceeds the
following ratio:
24 · Q
COMPTOT
M>= ---------------------
N
where:
M
= system water content [kg]
Q
COMPTOT
= unit cooling capacity [kW]
N
= number of capacity steps
If the water volume does not reach the value given by the formula, it is advisable to provide the circuit with a
storage vessel to increase the volume (tank + circuit) to match the result of the formula.
The chilled water piping and storage vessel must be insulated to prevent condensation on the pipe surfaces and
to avoid circuit performance losses.
It is mandatory to install a flow switch (supplied with the unit) on the
evaporator water outlet connection identified by the following decal:
EVAPORATOR WATER
It is compulsory to install a metallic filter, on the water inlet piping. If a
filter is not installed the warranty will be terminated immediately.
Summary of Contents for KAPPA V SR
Page 2: ......
Page 6: ......
Page 29: ...Blue Box 23 HYDRAULIC CIRCUIT DIAGRAM VERSION KAPPA V SR ST 2PS...
Page 40: ...Blue Box 34 ELECTRICAL PANEL LAY OUT MODELS 65 2 100 2...
Page 69: ...Blue Box 63 KAPPA V SR REFRIGERANT CIRCUIT...
Page 70: ...Blue Box 64 KAPPA V SR HP REFRIGERANT CIRCUIT...
Page 71: ...Blue Box 65 KAPPA V SR DC REFRIGERANT CIRCUIT...
Page 80: ...Blue Box 74...
Page 81: ......