Blue Box 42
5.2.3 Enabling the unit
Start-up of the unit from stand-by mode can be achieved after closing the external enabling contact, by pressing
the “ON/OFF” button, or by means of a signal on the serial line.
Activation of the controller outputs that manage the various sections of the chiller is executed in strict compliance
with the operating times. If the “ON” button is pressed before the external interlocks are closed, the display
indicates which of the external interlocks is not yet enabled.
Operation of the pump has priority to the compressors, which can start only after the pump is running.
5.2.4 Pump management (ST units only)
If system pump control is included switching on the unit will automatically enable the pump.
If there are two pumps (run and stand-by) they will be activated alternately when the programmed operating time
limit for each pump has elapsed.
When the pumps are switched over both pumps will run in tandem, for a few seconds, to ensure a constant flow
of water in the system circuit.
When the unit is switched from active status to stand-by, if performed by opening an external permissive, the
currently active pump of the ST unit will be stopped with a delay interval, after the disconnection of the last
compressor in operation, making it possible to exploit the thermal inertia of the system.
5.2.5 Compressor start-up
The controller allows the compressors to be started if the flow switch input is closed within the compressor start-
up delay time interval. If the flow switch input opens, after the compressor has started, the trip is retarded if it
occurs within the time programmed for the compressor stop.
If the unit trips due to the opening of the flow switch input, the relative alarm is displayed.
Starting and stopping of the compressors and capacity step control is managed by the controller in accordance
with the building cooling demands.
5.2.6 Chiller mode operation
In chiller operation, the controller lowers the water temperature value, maintaining it as close as possible to the
programmed set-point.
In the standard version, in which the control acts on the evaporator entering water, the management of compressor
operation and capacity steps is linked to the difference between the entering water temperature and the programmed
set-point.
5.2.7 Heat pump mode operation
In heat pump operation, the controller increases the water temperature value, maintaining it as close as possible
to the programmed set-point.
Management of compressor operation is performed in the same way as already illustrated for chiller mode
operation.
5.2.8
Evaporator low temperature chilled water protection
If the evaporator leaving water temperature is lower than the limit value programmed in the low temperature
chilled water protection set-point, the controller will stop all the compressors and activate the low temperature
water alarm.
This alarm must be reset manually and the compressor restarted only when the evaporator leaving water tempe-
rature is equal to or higher than the alarm trip value, increased by the low temperature water differential.
The low temperature water alarm can only be activated when the unit is switched on (in stand-by conditions the
freeze alarm is not operational).
5.2.9 Evaporator anti-freeze protection electric heater (optional)
Summary of Contents for KAPPA V SR
Page 2: ......
Page 6: ......
Page 29: ...Blue Box 23 HYDRAULIC CIRCUIT DIAGRAM VERSION KAPPA V SR ST 2PS...
Page 40: ...Blue Box 34 ELECTRICAL PANEL LAY OUT MODELS 65 2 100 2...
Page 69: ...Blue Box 63 KAPPA V SR REFRIGERANT CIRCUIT...
Page 70: ...Blue Box 64 KAPPA V SR HP REFRIGERANT CIRCUIT...
Page 71: ...Blue Box 65 KAPPA V SR DC REFRIGERANT CIRCUIT...
Page 80: ...Blue Box 74...
Page 81: ......