4. INSTALLATION
4.1 INSTALLATION CLEARANCES
It is important that an adequate air volume is available at the intake and exhaust sides of the condenser coil. It is
essential to avoid air recirculation between the intake and exhaust sides to prevent a reduction of the rated
performance levels and unit operating problems or a possible stop of normal unit operation. The minimum
clearances required for satisfactory operation of the unit is as follows (refer to figure 4):
-
coils side: minimum distance 0.75 meters.
- top: no impediments that obstruct the air discharge.
- electrical panel side: 1 meter (see dimensional drawings)
- hydraulic connection sides: 0,75 metre for pipe run location.
(*) It is recommended that sufficient space is allowed for shell and tube heat exchanger withdrawal.
High walls near the machine may interfere with correct functioning. When units are side by side the minimum
distance between them should be 3 metres (see figure 4).
Figure 4
SIDE BY SIDE UNITS
3 m min.
1.5 m
0.75 m (*)
1 m