Blue Box 59
SYMPTOM
OPERATION
PROBABLE CAUSE
POSSIBLE CORRECTIVE ACTION
COOLING
HEATING
R)
One or more
compressors switched
off. Display On with
⊗
⊗
Excess refrigerant charge
Check refrigerant charge and call
service organisation
alarm “High Pressure
Compressor”
⊗
⊗
Refrigerant circuit contains
non-condensable gas
Empty circuit, apply vacuum, and
recharge
⊗
⊗
High pressure switch
incorrectly set or faulty
Check pressure switch setting
⊗
Condenser coil or coil filters
(if present) clogged
Clean coil and filters (if present)
with compressed air
S)
One or more
compressors switched
⊗
⊗
Insufficient refrigerant
charge due to leak in circuit
Call service organisation
off. Display On with
alarm “Low Pressure
Compressors”
⊗
⊗
Thermostatic valve faulty
Call service organisation
⊗
⊗
Solenoid valve of liquid
refrigerant line faulty (if
present)
Call service organisation
⊗
Dehydrating filter clogged
Call service organisation
⊗
Evaporator coil or coil filters
(if present) clogged
Clean coil and filters (if supplied)
with compressed air
⊗
⊗
Liquid refrigerant valve not
completely open
Check and open fully
⊗
⊗
Pressostat faulty
Check; replace if necessary
T)
One or more
compressors switched
off. Display On with
alarm “Compressor
Thermal Protections”
⊗
⊗
Problems at the compressor Call service organisation
Summary of Contents for KAPPA V SR
Page 2: ......
Page 6: ......
Page 29: ...Blue Box 23 HYDRAULIC CIRCUIT DIAGRAM VERSION KAPPA V SR ST 2PS...
Page 40: ...Blue Box 34 ELECTRICAL PANEL LAY OUT MODELS 65 2 100 2...
Page 69: ...Blue Box 63 KAPPA V SR REFRIGERANT CIRCUIT...
Page 70: ...Blue Box 64 KAPPA V SR HP REFRIGERANT CIRCUIT...
Page 71: ...Blue Box 65 KAPPA V SR DC REFRIGERANT CIRCUIT...
Page 80: ...Blue Box 74...
Page 81: ......