Blue Box 57
SYMPTOM
OPERATION
PROBABLE CAUSE
POSSIBLE CORRECTIVE ACTION
COOLING
HEATING
K)
No compressor
running. Display On:
unit ON with alarm
“Exceeded Threshold
High Temperature of
⊗
Excessive thermal load
Wait until entering water
temperature is below the alarm
set point. Start hydraulic circuit
of evaporator and unit. If not
sufficient contact assistance.
entering User Water
⊗
Refrigerant circuits partially
discharged
Call assistance
L)
No compressor
running. Display On:
unit ON with alarm
⊗
⊗
Power supply voltage not
stable
Check power supply voltage; if
not correct contact the electricity
company
“No power to
Control circuits”
⊗
⊗
Fuses FU51 burnt-out
Check cause of fuse burn-out
and replace fuses.
M)
No compressor
running.
⊗
⊗
No water flow to
evaporator
Check hydraulic circuit
Display On: unit
OFF with alarm
“Flow Switch Alarm”
⊗
⊗
Flow switch faulty
Check flow switch contact and
replace if necessary
N)
No compressor
running. Display On:
unit OFF with alarm
”Incorrect Phase
Sequence” and phase
sequence relay with
green LED On and
orange LED Off
⊗
⊗
Incorrect phase sequence
Invert two of the phase wires of
the power supply line
Summary of Contents for KAPPA V SR
Page 2: ......
Page 6: ......
Page 29: ...Blue Box 23 HYDRAULIC CIRCUIT DIAGRAM VERSION KAPPA V SR ST 2PS...
Page 40: ...Blue Box 34 ELECTRICAL PANEL LAY OUT MODELS 65 2 100 2...
Page 69: ...Blue Box 63 KAPPA V SR REFRIGERANT CIRCUIT...
Page 70: ...Blue Box 64 KAPPA V SR HP REFRIGERANT CIRCUIT...
Page 71: ...Blue Box 65 KAPPA V SR DC REFRIGERANT CIRCUIT...
Page 80: ...Blue Box 74...
Page 81: ......