Blue Box 37
Figure 11
4.15 ELECTRICAL CONNECTIONS
4.15.1 General
Electrical connections must be made in accordance with the information given on the electrical drawing attached
to the unit and in compliance with the applicable local regulations.
An Earth (ground) connection is compulsory. The installer must connect the earth cable with a dedicated terminal
on the earth bar in the electrical board (refer to the illustration on the following page) labelled PE.
It must be verified that the electrical supply corresponds to the unit electrical nominal data (tension, phases,
frequency) indicated on the label on the front panel of the unit.
Line voltage fluctuations must not be more than ±5% of the nominal value, while the voltage unbalance between
one phase and another must not exceed 2%. If these tolerances are not possible contact Blue Box to provide the
necessary devices.
Check that the line is connected with the correct phase sequence.
The cable inlet point is created by drilling a hole in the side or base of the electrical enclosure, depending on the
model.
The control circuit is derived from the power supply through a transformer located inside the electrical panel.
The control circuit is protected by fuses.
Electrical cable anchorage: anchor the electrical power cables with fixing
systems able to withstand pulling and torsional stress.
Before any operation on the electrical section, be sure that the electric
supply is disconnected.
Power cable and line protection must be sized according to the
specification indicated on the wiring diagram and the documents supplied
with the unit.
The crankcase heaters must be connected at least 12 hours before starting
the unit; the heaters are automatically connected when the main
disconnect switch is set to the ON position.
The electrical supply must be within the limits shown. If this is not the
case the warranty will be terminated immediately.
4.15.2 Power supply to crankcase heaters
1) Close the main disconnect switch by turning it from position “0” to position “1”
2) Check that the word “OFF” is shown on the display
3) Ensure that the unit is in “OFF” status and that the external enabling contact
is open
4) After a few moments, if the phase sequence is incorrect the alarm “INCORRECT
PHASE SEQUENCE” will be displayed. In this case invert the connections of
two of the power line phase wires.
5) Leave the unit in this condition for at least 12 hours to allow the crankcase
heaters to perform their function
Summary of Contents for KAPPA V SR
Page 2: ......
Page 6: ......
Page 29: ...Blue Box 23 HYDRAULIC CIRCUIT DIAGRAM VERSION KAPPA V SR ST 2PS...
Page 40: ...Blue Box 34 ELECTRICAL PANEL LAY OUT MODELS 65 2 100 2...
Page 69: ...Blue Box 63 KAPPA V SR REFRIGERANT CIRCUIT...
Page 70: ...Blue Box 64 KAPPA V SR HP REFRIGERANT CIRCUIT...
Page 71: ...Blue Box 65 KAPPA V SR DC REFRIGERANT CIRCUIT...
Page 80: ...Blue Box 74...
Page 81: ......