Blue Box 55
SYMPTOM
OPERATION
PROBABLE CAUSE
POSSIBLE CORRECTIVE ACTION
COOLING
HEATING
E)
No compressor
running. Display On:
⊗
⊗
220V fuses burnt-out
(FU51)
Change fuses. If fuses burn-out
again, contact assistance
unit ON with alarm
“High Pressure
Compressor 1, 2, 3”
⊗
Fans contactor not
energised
Check voltage across the
contactor coil and coil continuity
⊗
Fan fuses burnt-out (FU21) Check cause of burn-out and
change fuses.
⊗
Fan motor faulty
Check and replace if necessary
F)
No compressor
running. Display On:
unit ON with alarm
“Fans protection”
⊗
⊗
Fan thermal protection
intervention
Check insulation between
windings and from windings to
earth (ground)
⊗
⊗
Fan motor faulty
Check and replace if necessary
⊗
⊗
Faulty fan alarm relay
Check and replace relay
G)
No compressor
running. Display On:
unit ON with alarm
⊗
⊗
Drop in power feeding
voltage
Check voltage stability and fit
appropriate protection if
necessary
“Thermal protections
Compressor 1, 2, 3”
⊗
⊗
Setting of thermal
protections
Contact assistance
⊗
⊗
Circuits partially discharged Call service to replenish charge
Summary of Contents for KAPPA V SR
Page 2: ......
Page 6: ......
Page 29: ...Blue Box 23 HYDRAULIC CIRCUIT DIAGRAM VERSION KAPPA V SR ST 2PS...
Page 40: ...Blue Box 34 ELECTRICAL PANEL LAY OUT MODELS 65 2 100 2...
Page 69: ...Blue Box 63 KAPPA V SR REFRIGERANT CIRCUIT...
Page 70: ...Blue Box 64 KAPPA V SR HP REFRIGERANT CIRCUIT...
Page 71: ...Blue Box 65 KAPPA V SR DC REFRIGERANT CIRCUIT...
Page 80: ...Blue Box 74...
Page 81: ......