18

5.4 Charging refrigerant

Charge only permitted refrigerants
(see chapter 2).

• Before refrigerant is charged:

- Energize the crankcase heater.
- Check the compressor oil level.
- Do not switch on the compressor!

• Charge liquid refrigerant directly

into the condenser resp. receiver.
For systems with flooded evapora-
tor refrigerant can be also charged
into the evaporator.

• After commissioning it may be nec-

essary to add refrigerant:
Charge the refrigerant from the
suction side while the compressor
is in operation. Charge preferably at
the evaporator inlet.
Blends must be taken from the 
charging cylinder as "solid liquid".

If liquid is charged:

Attention!
Danger of wet operation!
Charge small amounts at a time!
Keep the oil temperature above
40°C.

Danger!
Explosion risk of components
and pipelines by hydraulic over-
pressure.
Avoid absolutely overcharging of
the system with refrigerant!

5.5 Checks before starting

• Oil level

(within range on sight glass)

When exchanging a compressor:

Attention!
Oil is already in the system.
Therefore it may be necessary
to drain a part of the oil charge.
If there are large quantities of oil
in the circuit (possibly from a
preceding compressor damage),
there is also a risk of liquid slug-
ging at start.
Adjust oil level within the marked
sight glass range!

!

!

!

!

5.4 Remplir le fluide frigorigène

Remplir seulement des fluides frigori-
gènes autorisés (voir chapitre 2).

• Avant remplir le fluide frigorigène:

- Enclencher la résistance de carter.
- Contrôler le niveau d'huile dans le

compresseur.

- Ne pas enclencher le compresseur !

• Remplisser le fluide frigorigène liquide

directement dans le condenseur resp.
le réservoir de liquide. Pour les sys-
tèmes avec évaporateur noyé, le rem-
plissage peut aussi se faire dans l'éva-
porateur.

• Après la mise en service, il peut s'avé-

rer nécessaire de procéder à un
appoint de fluide frigorigène:
Le compresseur étant en service,
introduire le fluide frigorigène du côté
aspiration, de préférence à l'entrée de
l'évaporateur. Les mélanges doivent
être retirées du cylindre de remplissa-
ge en phase liquide et sans bulles.

En cas de remplissage en phase liquide:

Attention !
Risque de fonctionnement en noyé !
Faire un dosage très fin.
Maintenir la température d'huile au-
dessus de 40°C.

Danger !
Danger d'éclatement des compo-
sants et conduites par surpression
hydraulique.
Eviter absolument suralimentation
du système avec fluide frigorigène !

5.5 Contrôles avant le démarrage

• Niveau d'huile

(dans la plage indiquée sur le voyant)

En cas de remplacement du compresseur:

Attention !
Il y a déjà de l’huile dans le circuit.
Pour cette raison il peut être néces-
saire de retirer une certaine quantité
d’huile.
Quand il y a des quantités importan-
tes d’huile dans le circuit (p. ex. à la
suite d’un défaut du compresseur), il
existe un danger supplémentaire de
coups de liquide au démarrage.
Ajuster le niveau d’huile dans la
plage indiquée sur le voyant !

!

!

!

!

5.4 Kältemittel einfüllen

Nur zugelassene Kältemittel einfüllen
(siehe Kapitel 2).

• Bevor Kältemittel eingefüllt wird:

- Ölsumpfheizung einschalten.
- Ölstand im Verdichter kontrollie-

ren.

- Verdichter nicht einschalten!

• Flüssiges Kältemittel direkt in den

Verflüssiger bzw. Sammler füllen,
bei Systemen mit überflutetem
Verdampfer evtl. auch in den Ver-
dampfer.

• Nach Inbetriebnahme kann es not-

wendig werden, Kältemittel zu
ergänzen:
Bei laufendem Verdichter Kälte-
mittel auf der Saugseite einfüllen,
am besten am Verdampfer-Eintritt.
Gemische müssen dem Füllzylin-
der als blasenfreie Flüssigkeit ent-
nommen werden.

Bei Flüssigkeits-Einspeisung:

Achtung!
Gefahr von Nassbetrieb!
Äußerst fein dosieren!
Öltemperatur oberhalb 40°C
halten.

Gefahr!
Berstgefahr von Komponenten
und Rohrleitungen durch hydrau-
lischen Überdruck.
Überfüllung des Systems mit
Kältemittel unbedingt vermeiden!

5.5 Kontrollen vor dem Start

• Ölstand

(im markierten Schauglasbereich)

Bei Verdichter-Austausch:

Achtung!
Es befindet sich bereits Öl im
Kreislauf. Deshalb kann es erfor-
derlich sein, einen Teil der Ölfül-
lung abzulassen.
Bei größeren Ölmengen im
Kreislauf (z. B. durch vorausge-
gangenen Verdichterschaden)
besteht zudem Gefahr von Flüs-
sigkeitsschlägen beim Start-
vorgang.
Ölstand innerhalb markiertem
Schauglasbereich halten!

!

!

!

!

KB-110-6

Summary of Contents for 2HL-1.2

Page 1: ...e only if they have been in stalled in these machines according to the existing instruction and as a whole agree with the corresponding provisions of legislation standards to apply refer to Manufactur...

Page 2: ...ncern Les indications de s curit sont des instructions pour viter les mises en danger Respecter scrupuleusement les indica tions de s curit Attention Instruction pour viter une possible mise en danger...

Page 3: ...ion Chemical reactions possible as well as increased condensing pressure and discharge gas temperature Warning In case of air admission a critical shift of the refrigerant ignition limit is possible A...

Page 4: ...resseur peut tre mont rigide s il n y a aucun risque de rupture par vibrations dans le r seau de tuyauteries raccord Dans le cas contraire le montage doit se faire sur des amortisseurs Ceci est parti...

Page 5: ...02 4G 30 2 Y braun brown brun 370 004 01 blau blue bleu 370 004 03 6J 22 2 Y 6F 50 2 Y braun brown brun 370 004 01 blau blue bleu 370 004 03 8GC 50 2 Y 8FC 70 2 Y rot red rouge 370 004 02 schwarz blac...

Page 6: ...ent fernen I sst Unterlagscheibe entfernen Schwingungsd mpfer Typ III Tandems oder Sonderzubeh r Vor Transport Selbstsichernde Mutter anzie hen bis das Element ca 1 bis 2 mm zusammengedr ckt ist Nach...

Page 7: ...ning suction side filter mesh size 25 m Attention Compressor damage possible Generously sized high quality fil ter driers must be used to ensure a high degree of dehy dration and to maintain the chemi...

Page 8: ...ssemblage cor rect Voir figure 4 D marrage vide SU Accessoire particulier de 2U 3 2 Y 6F 50 2 Y En cas de montage ult rieur une chan ge du t te de culasse est n cessaire Montage voir chapitre 3 4 Comp...

Page 9: ...re cooling with R22 R404A R507A upon request The suction gas is directly led into the cylinders This operation mode always requires external air cooling either by additional fan or location of the com...

Page 10: ...F 7 1 6 2 0 U N F 1 1 7 1 6 2 0 U N F 1 2 3 8 1 4 N P T F 9 b 1 2 1 4 N P T F 5 1 4 1 8 N P T F 4Z 5 2 Y 4N 20 2 Y 4J 13 2 Y 4G 30 2 Y 5 8 3 LP 1 HP 1 4 18 NPTF 1 8 27 NPTF 1 8 27 NPTF 3 8 18 NPTF 10...

Page 11: ...1 8 2 7 N P T F 3 L P M 2 0 x 1 5 1 6 D L 8 D L S L 3 8 1 8 N P T F 1 8 2 7 N P T F 3 L P Sonstige Anschl sse wie beim entsprechenden Einzelverdichter Other connections same as for the corresponding...

Page 12: ...e Kabel Durch f hrungen verwenden und auf gute Abdichtung bei der Montage achten Elektrische Kabel Verbindungen auf festen Sitz pr fen Bei der Dimensionierung von Motor sch tzen Zuleitungen und Sicher...

Page 13: ...e indications on the terminal box cover Part winding motor Closely observe part winding order First part winding contactor K1 connections 1U1 1V1 1W1 Second part winding contactor K2 connections 2U1 2...

Page 14: ...chnique KT 122 SE B2 2HL 1 2 Y 2N 7 2 Y 4Z 5 2 Y 6F 50 2 Y 8GC 50 2 Y 8FC 70 2 Y est log dans la bo te de connexion Les c bles des sondes PTC CTP du moteur sont raccord s Autres connexions confor m me...

Page 15: ...s sor long shut off periods high refrigerant charge danger of refrigerant condensation into the compressor Pressostat diff rentielle d huile pour compresseurs avec pompe huile partir de 2U 3 2 Y Pour...

Page 16: ...usement s ch en usine son tanch it est contr l e et il est rempli avec un gaz de protection N2 Attention Essayer la r sistance la pression et l tanch it de toute l installation pr f remment avec l azo...

Page 17: ...r parts of it according to EN 378 2 or valid equiv alent safety standards by using pre ferably an overpressure of dry nitro gen Danger Test pressures and safety refer ences see chapter 5 1 5 3 Evacuat...

Page 18: ...doivent tre retir es du cylindre de remplissa ge en phase liquide et sans bulles En cas de remplissage en phase liquide Attention Risque de fonctionnement en noy Faire un dosage tr s fin Maintenir la...

Page 19: ...4 to 3 5 bar Minimum permissible inlet pressure suction side of oil pump 0 4 bar Automatic monitoring by differential oil pressure switch differential cut out pressure 0 7 bar time delay 90 s When th...

Page 20: ...mponets de l installation viter des vibrations fortes Nombre d enclenchements Le compresseur ne doit pas tre mis en service que 8 fois par heure En plus une dur e de marche minimale doit tre assu r e...

Page 21: ...er operation Bubble free refrigerant at expan sion valve Avoid refrigerant migration high pressure to low pressure side dur ing longer shut off periods Application of a crankcase heater Pump down syst...

Page 22: ...de surpression incorpor e Cette soupape n exige aucun entretien Cependant des fuites permanentes peu vent se produire apr s l avoir crach e plusiers reprises en raison des conditions de service anorma...

Page 23: ...nt ling necessary or when decommis sioning them Close the shut off valves at the com pressor Pump off the refrigerant Do not release the refrigerant but dispose it properly Warning Compressor can be u...

Page 24: ...n Subject to change Toutes modifications r s rv es 04 06 80410101 Bitzer K hlmaschinenbau GmbH Eschenbr nnlestra e 15 71065 Sindelfingen Germany fon 49 0 7031 932 0 fax 49 0 7031 932 146 147 www bitze...

Reviews: