MK / MKT (E5) 03/2019
page 66/158
10.6.4 Setpoint entry
•
Select the field “Temperature” and enter the desired temperature setpoint.
Setting range:
MK
-50 °C /
-58°F
up to 180 °C /
356 °F
,
MKT:
-80 °C /
-112 °F
up to 180 °C /
356 °F:
Confirm entry with
Confirm
icon. The controller returns to the section view.
•
MK 56:
Select the field “Fan” and enter the desired fan speed setpoint.
Setting range: 30% up to 100% fan speed.
Confirm entry with
Confirm
icon. The controller returns to the section view.
10.6.5 Special controller functions via operation lines
You can define the switching state of up to 16 operation lines (control contacts). They are used to activate
/ deactivate special controller functions.
•
Operation line “Idle mode” activates / deactivates the operating mode “Idle mode”.
•
Operation lines „Switching output 1“ up to „4“ can be used to turn on and off any equipment connected
to the zero-voltage switching outputs (DIN sockets (7) and (8) (option, chap. 19).
•
Operation line “Compr. air dryer” serves to activate the compressed air dryer (option, chap. 20.6).
•
Operation line “Compressed air valve” serves to open the solenoid valve of the compressed air con-
nection (for options compressed air connection, chap. 20.5, or compressed air dryer, chap. 20.6)
•
Operation line “Anti-condensation protection” serves to switch the anti-condensation protection (chap.
The other operation lines are without function.
Select the desired program and section. You can set the operation lines in the “Functions on/off” field.
For details please refer to chap. 9.7.3.
Summary of Contents for MK 115
Page 138: ...MK MKT E5 03 2019 page 138 158 24 12 Dimensions MK 56 dimensions mm ...
Page 139: ...MK MKT E5 03 2019 page 139 158 MK MKT 115 dimensions mm ...
Page 140: ...MK MKT E5 03 2019 page 140 158 MK 240 dimensions mm ...
Page 141: ...MK MKT E5 03 2019 page 141 158 MKT 240 dimensions mm ...
Page 142: ...MK MKT E5 03 2019 page 142 158 MK MKT 720 dimensions mm ...
Page 144: ...MK MKT E5 03 2019 page 144 158 ...
Page 145: ...MK MKT E5 03 2019 page 145 158 ...
Page 146: ...MK MKT E5 03 2019 page 146 158 25 2 EU Declaration of Conformity for MKT ...
Page 147: ...MK MKT E5 03 2019 page 147 158 ...
Page 148: ...MK MKT E5 03 2019 page 148 158 ...
Page 150: ...MK MKT E5 03 2019 page 150 158 ...
Page 151: ...MK MKT E5 03 2019 page 151 158 26 Product registration 26 1 Registering a BINDER chamber ...
Page 159: ......