FONTE 11-14 AP

11

Fig.2

Flue gas release safety device

Release hood  

Heat exchanger  

Ignition electrode

Burner

Hydraulic valve

Temperature regulator

Gas valve

Gas input

10  Gas adjustment screws

11  Electronic devices

12  Battery box 

13  Economiser

14  Gas pressure intake

15  Pilot burner

2. INSTALLATION

2.a  Regulations (Fig.3)

The  use  of  gas  devices  is  controlled  by  precise  regulations.    It  is 

essential to observe regulations in force.

Installation of liquid petroleum gas (L.P.G) must comply with all the 

distributor’s requirements and those of the regulations.

2.b  Wall mounting (Fig.4)

Warning 
Do not install this device in an area that contains dust, greasy 

vapour and/or corrosive elements. 

 

-  The device must be installed on a suitable wall surface in proximi

-

ty to a fume disposal flue. 

-  It  is  vital  to  leave  the  minimal  distances  around  the  device  as 

shown in fig 3 to allow for maintenance operations to take place.

Location

-  The water heater must not be tightly placed in an enclosure or 

slot, it should have an adequate flow of air around it (fig.  4) 

-  The water heater must not be placed above a kitchen or other 

cooking devices that might deposit grease vapour on its exterior 

leading to corrosion 

-   surfaces  that  sensitive  to  heat  (e.g.  wood)  must  be  protected 

using appropriate insulation.

-  Fig. 4 displays the dimensions necessary for wall mounting

11

14

C

244

274

E

605

640

F

150

155

2.c  Room ventilation

The installation of the water heater must comply with regulations in 

force including any updates. See paragraph 2.a

Warning: 

This device can only be installed in venues that are per

-

manently ventilated according to regulation in force. 

Air circulation

It is vital that areas where gas devices are installed (type B) have 

access to the amount of air necessary for the regular combustion of 

gas as well as the ventilation of the venue.

-  It is prohibited to use an extractor fan, fireplaces and other similar 

devices at the same time as the water heater

-  The area where the water heater is installed must have a regular 

flow of air for ventilation.

Air flow

The flow of air must occur by the following means:

-  Permanent openings in the wall that lead outdoors;

-  Single or collective ventilation ducts.

The air used for ventilation must be taken directly from an outside 

location, that is far from sources of pollution.

Indirect ventilation from adjacent areas are permitted with the fol

-

lowing limitations:

-  the adjacent area is equipped with direct ventilation;

-  the devices within the area to ventilate are connected to a waste 

duct;

-  the adjacent area does not contain a bedroom and is not a com

-

mon area;

-  the adjacent area is not a fire hazard such as a storage area for 

flammable materials, garage etc.

-  the adjacent area is not lower than the area to ventilate as this 

might lead to an opposing draught (this can be caused by other 

devices that operate on the basis of combustion, a fireplace or any 

suction device that have not been given an adequate air supply);

-  The air flow from the adjacent area occurs freely through perma

-

nent openings.

2.d Gas Connection

See paragraph 2.a

Determine the pipe diameter according to current regulations.  Befo

-

re installing the device blow in the gas pipe to eliminate any residue 

from  its  manufacturing.    Connect  the  water  heater  to  the  internal 

system’s gas pipes and place a tap above the device for the halting 

and release of gas. 

The water heaters that are powered by tanks of L.P.G. gas with re

-

gulation and interception devices, must be connected  correctly so to 

guarantee the safety of persons and the surrounding area.  

Follow all related regulations.

When initially installing the device qualified persons must perform 

the following tests: 

-  Check that the internal and external parts of the gas supplying 

device are sealed; 

-  check that the gas quantity supplied is equal to that required by 

the device; 

-  check that the device receives the type of gas it is manufactured 

to process;

-  check that the gas supply pressure does not go beyond the maxi

-

mum pressure values displayed on the information plate; 

-  check that the gas supply system supplies the necessary amount 

of gas to the device and that it is equipped with all the necessary 

safety devices prescribed by current regulations.

If the user is absent for a lengthy period, turn off the main gas supply tap.  

Do not obstruct the area’s ventilation openings where the device is 

installed to avoid dangers such as the build up of toxic and explosive 

substances.

Do not utilize gas tubes to earth electrical devices.

Product datasheet - Description

Fonte 11 AP

Fonte 14 AP

Water heating energy efficiency class

-

B

B

-

Declared load profile

-

M

XL

-

Water heating energy efficiency class 

ηwh

59,5

73,7

%

Daily fuel consumption

Qfuel

11,018

27,893

kWh

Annual fuel consumption

AFC

8

20

GJ

Indoor sound power level

LWA

56

59

dB(A)

Nitrogen oxide emissions

NOx

114

120

mg/kWh

Summary of Contents for FONTE 11 AP

Page 1: ...FE BAIN INSTANTANE A GAZ MANUEL POUR L INSTALLATION ET L ENTRETIEN MANUAL DE INSTALACI N USO Y MANTENIMIENTO ESQUENTADOR INSTANT NEO A G S MANUAL PARA A INSTALA O O USO E A MANUTEN O YEBLIKKELIG VARMT...

Page 2: ...s que deben re alizarse con cuidado y con una adecuada preparaci n PROHIBIDO para acciones NO se tienen que realizar La marcaci n CE situada en el producto indica que el mismo es conforme a las siguie...

Page 3: ...pag 23 2 c Ventilaci n de los locales pag 23 2 d Conexi n del gas pag 23 2 e Conexi n del agua pag 24 2 f Evacuaci n de los productos de la combusti n pag 24 2 g Transformaci n del gas pag 24 SV 3 PU...

Page 4: ...a calda deve quindi es sere allacciato ad una rete di distribuzione d acqua calda sanitaria compatibilmente alle sue prestazioni ed alla sua potenza In caso di fuoriuscite d acqua chiudere l alimentaz...

Page 5: ...lusso naturale dell aria deve avvenire per via diretta attraverso aperture permanenti praticate su pareti del locale da ventilare che danno verso l esterno condotti di ventilazione singoli oppure coll...

Page 6: ...carico eccessivi cambi di direzione curve contropendenze Tutto questo provoca delle considerevoli perdite di carico che ostacolano il flusso verso l esterno dei prodotto della combustio ne L intervent...

Page 7: ...temperatura dell acqua erogata Gli scaldabagni sono apparecchi a variazione automatica di po tenza di tipo PROPORZIONALE cio in grado di adeguare il consumo del gas modulazione di fiamma ai prelievi d...

Page 8: ...chiudendo il rubinetto del gas In particolare controlla re il bruciatore principale e la fiamma pilota l elettrodo di accensio ne la valvola di sicurezza e la tenuta del circuito gas Verificare che no...

Page 9: ...ola acqua blocca to in apertura smontare pulire ed eventualmente sostituire nella versione a GPL controllare la pressione di alimentazione gas regolare e nel caso sostituire il regolatore di pressione...

Page 10: ...e connected to a water distribution network who s load and settings are compatible with the product If water spills turn off the water supply and advise the qualified personnel at the Technical Assist...

Page 11: ...ndirect ventilation from adjacent areas are permitted with the fol lowing limitations the adjacent area is equipped with direct ventilation the devices within the area to ventilate are connected to a...

Page 12: ...re the device is installed To again use the product it is necessary to follow the instructions in the paragraph OPERA TION If the device or its electrical connections breaks down the machine operation...

Page 13: ...ROPOR TIONAL able to change the gas consumption modulating the flame to respond to the amount of water extracted Model 11 for the extraction of 2 5 to 5 5 l m the temperature of the water supplied rem...

Page 14: ...once a year Before cleaning or performing maintenance opening or disassem bling the panels switch off the device and turn off the gas supply Check the main burner and the pilot flame the ignition ele...

Page 15: ...gas shutter test clean valve piston or stem is locked in open posi tion disassemble clean and eventually substitute If an LPG supply check the gas pressure regulate and if necessary substitute the ta...

Page 16: ...t tre branch un r seau de distribution d eau chaude sanitaire conform ment ses prestations et sa puissance En cas de sorties de l eau couper l alimentation hydrique et avertir imm diatement le personn...

Page 17: ...anentes pratiqu es sur des parois du local ven tiler qui donnent vers l ext rieur conduits de ventilation individuels ou bien collectifs ramifi s L air de ventilation doit tre pr lev directement de l...

Page 18: ...uit d vacuation et le carneau montant Le dispositif de contr le est constitu d un thermostat raccord en s rie au thermocouple L intervention du dispositif de contr le en provoquant l interruption du t...

Page 19: ...de la demande d eau chaude le br leur principal s teint reste toutefois allum e la flamme pilote et l appareil est disponible pour des demandes successives L extinction accidentelle de la flamme du p...

Page 20: ...eau pr sente l int rieur 4 ENTRETIEN Pour un usage correct dans le temps faire ex cuter un contr le de l appareil par du personnel qualifi au moins une fois par an Avant d effectuer toute op ration d...

Page 21: ...de la vanne eau bloqu en ouverture d monter nettoyer et ventuellement rem placer dans la version GPL contr ler la pression d alimentation gaz r gler et le cas ch ant remplacer le r gula teur de press...

Page 22: ...irve para producir agua caliente debe ser co nectado a una red de distribuci n de agua caliente sanitaria dimensionada a sus prestaciones y su potencia En caso de p rdidas de agua hay que cerrar la al...

Page 23: ...ha de tomarse directamente del exterior en una zona situada lejos de fuentes de contaminaci n Tambi n se puede realizar la ventilaci n indirecta tomando el aire de locales adyacentes al local que se...

Page 24: ...n del di metro del conducto de humos excesivos cambios de direcci n curvas contrapendientes Todo esto provoca considerables p rdidas de carga que obstaculi zan el flujo de los productos de la combust...

Page 25: ...uipo est en condiciones de su ministrar agua caliente a cada demanda En efecto la apertura del grifo del agua provoca el encendido del quemador principal mientras que cerrando el grifo al finalizar la...

Page 26: ...to del aparato es necesario realizar una revisi n anual por el Servicio T cnico Oficial o mantenedor au torizado Antes de efectuar cualquier operaci n de limpieza mantenimiento apertura o desmontaje d...

Page 27: ...illa de la v lvula del agua bloque ada en apertura desmontar limpiar y eventualmente sustituir en la versi n de GLP controle la presi n de alimentaci n del gas regular y de ser necesario sustituir el...

Page 28: ...de de distribui o de gua quen te sanit ria compativelmente com o seu desempenho e sua pot ncia Em caso de vazamentos de gua fechar a alimenta o hi dr ulica e avisar tempestivamente o pessoal qualifica...

Page 29: ...amificados O ar de ventila o deve ser aspirado do externo em zona afastada de fontes de polui o Tamb m permitida a ventila o indirecta por meio de aspira o de ar de locais cont guos quele a ser ventil...

Page 30: ...ntrolo provocando a interrup o do termopar intercepta o fluxo de g s tanto no queimador principal quanto na chama piloto A interven o do di spositivo de controlo pode ser provocada por uma obstru o to...

Page 31: ...imento do queimador principal enquanto fechando a mesma torneira terminada a necessidade de gua quente o queimador principal desliga por m permanece acesa a chama piloto e o aparelho encontra se dispo...

Page 32: ...lo de toda a gua que cont m 4 MANUTEN O Para um uso correcto no tempo fazer com que pessoal qualificado execute um controlo do aparelho pelo menos uma vez por ano Antes de efectuar qualquer opera o de...

Page 33: ...la gua bloqueado na abertura Desmontar limpar e eventualmente substituir Na vers o com GLP controlar a press o de alimenta o g s Regular e se necess rio substituir o regula dor de press o da botija At...

Page 34: ...ann det m derfor tilkobles et forsyningsnett med varmt vann i samsvar med dets ytelser og kraft I tilfelle vannlekkasje m vanntilf rselen stenges av og kyndig personale hos Teknisk Assistanse m varsle...

Page 35: ...gskilder Indirekte ventilasjon er ogs tillatt via opptak av luft fra n rliggende rom til det som skal luftes ut med de advarsler og begrensninger som beskrives her Rommet ved siden av m v re utstyrt m...

Page 36: ...t mmer ret Fo store retningsendringer svinger motbakker Alt dette for rsaker betydelige mengder last som forhindrer str m ningen utover av forbrenningsgassene Inngripen av styreinnret ningen stopper...

Page 37: ...n A mot stor flamme under roteringen ved den lille flammen m det trykkes lett p knotten og roteringen kan fortsette Fra n av er apparatet i stand til levere varmt vann ved hver foresp rsel pningen av...

Page 38: ...HOLD For en korrekt bruk over tid la kyndig personale foreta en kontroll av apparatet minst n gang i ret F r ethvert inngrep med rengj ring vedlikehold pning eller de montering av varmtvannsberedens p...

Page 39: ...r stang til vannventilen forriglet ved pning demontere rengj re og skift eventuelt ut I versjonen med PLG kontrollere gassens matetrykk Justere og eventuelt skift ut gassflaskens trykkregulator Tennin...

Page 40: ...kerhetsanordnin gar och automatiska reglerdon under hela anl ggningens livsl ngd f rutom av tillverkaren Denna apparat r avsedd att producera varmvatten och ska d rmed anslutas till ett distributions...

Page 41: ...ventilering r till ten genom att ta luft fr n intilliggande lokaler i f rh llande till den som ska ventileras och genom att f lja nedan angivna f reskrifter och villkor Den intilliggande lokalen ska v...

Page 42: ...eter p r kkanalen f r m nga riktnings ndringar kurvor Motsatt lutning Samtliga ovan n mnda punkter orsakar anm rkningsv rda str m ningsf rluster som f rs mrar f rbr nningsproduktens fl de mot skorsten...

Page 43: ...n mnda f rfarandet tills l gan t nds utan att sl ckas Vrid reglaget A mot den stora flamman F r att kunna vrida den r det n dv ndigt att trycka in reglaget n got i n rheten av den lilla l gan och sed...

Page 44: ...kt funktion under l ng tid ska du l ta en kvalifice rad tekniker kontrollera apparaten minst en g ng om ret Innan n got arbete p b rjas som r r reng ring underh ll ppning av varmvattenberedarens panel...

Page 45: ...t i p pet l ge ta bort reng r och byt eventuellt ut p gasoldrivna versioner ska trycket p ga stillf rseln kontrolleras justera gasbeh llarens tryckregulator och byt ut vid behov F rdr jd t ndning trot...

Page 46: ...4 Misure in mm Measures in mm Mesures en mm Medidas en mm Medidas em mm M l i mm M tt i mm B A F E 87 H G 41 130 D C A B C D E F G H 11 592 110 101 245 314 128 54 84 14 650 130 101 245 363 148 74 104...

Page 47: ...47 Fig 7 Fig 13 Fig 8 Fig 11 Fig 14 Fig 9 Fig 16 A B Fig 6 Fig 12 Fig 10 B Fig 15...

Page 48: ...Cod BER _ EXP _ PIEZO _ 1 ED 13 06 15...

Reviews: