Bennett CNG Spec. 100 Series Operators Manual
Programming
23
MENU CODE 10 – HOW TO SET THE END, MID, LOW , OR HIGH FLOW RATE
Menu Code 10 changes the flow rate at which the dispenser will determine that the vehicle tank is full. The dispenser will continue to fill
as long as the measured flow rate remains above this set point. It also sets the maximum flow rate allowed before displaying a High Flow
Error (Error 21).
End Flow
– Greater than or equal to (>=) the minimum flow rate for mass units.
Mid Flow (2
nd
Flo)
– Greater than or equal to (>=) the minimum flow rate for mass units.
Note:
For CNG 3-Bank Only!
Low Flow (1
st
Flo)
– Greater than or equal to (>=) the minimum flow rate for mass units
Note:
For CNG 3-Bank Use Only!
High Flow (HI Flo)
- Less than or equal to (<=) the minimum flow rate for CNG (250).
TO SELECT A END, MID, LOW, OR HI GH FLOW AMOUNT IN GALLONS OR LITERS IN MENU CODE 10, FOLLOW THIS
PROCEDURE:
1.
After the Menu Code has been accessed, press the number
1
and
0
button and then
the [
MODE
] button on the keypad. The main display on an un-programmed
dispenser will appear as in
Figure 4.23
. This is the factory default setting. The PPM
display shows the dispenser is in Menu Code 10.
2.
To change the setting, use the
0
through
9
buttons on the keypad to enter a value in
seconds.
Note
: If an error is made, press the correct number. The new number
replaces the error.
3.
When the correct value appears in the mass display, press the [
ENTER
] button to save
the new setting and to cycle to the next option as shown in
Figures 4.24
,
4.25
, and
4.26
.
NOTE:
If an error is made, enter a new number until the correct number
of seconds appear in the mass display.
4.
Press the [
CANCEL
] button to exit this Menu Code.
FIGURE 4.23 –END FLOW TIME OUT
FIGURE 4.24 –MID FLOW TIME OUT
Sale $
end flo
GGE
0.4
code
-10
Sale $
2nd flo
GGE
3.0
code
- 10
Sale $
1st flo
GGE
4.0
code
- 10
Sale $
hi flo
GGE
020
code
- 10
FIGURE 4.25 –LOW FLOW TIME OUT
FIGURE 4.26 –HIGH TIME OUT
Summary of Contents for CNG Spec. 100 Series
Page 3: ...Bennett CNG Spec 100 Series Operators Manual Bennett Limited Warranty i...
Page 4: ...Bennett CNG Spec 100 Series Operators Manual ii Page Intentionally Left Blank...
Page 46: ...Bennett CNG Spec 100 Series Operators Manual Programming 40 Page Intentionally Left Blank...
Page 56: ...Bennett CNG Spec 100 Series Operators Manual Diagnostics 50 Page Intentionally Left Blank...