Product overview
EM7004
18
Version: 2.0
Sample
Value in object
= 0x00FF, outputs 0-7 are assigned to the PLS function, outputs 8-15 are
not linked to the function.
If no valid table entry is available (counter reading >=0, but less than the first table entry), the value in object
Object
contains up to 75 switch values ("PLS switch values"); object
contains
up to 75 output data ("PLS output data"). The PLS function can only be activated if the subindex :0 (number
of following subindices) for objects
Note
PLS function: Response time for triggering the outputs
The internal processing time of the terminal from reaching the PLS switch value to switch-
ing of the digital outputs is specified with less than 365 µs.
Code Word
Note
Code word
The vendor reserves the authority for the basic calibration of the terminals. The code word
is therefore at present reserved.