Appendix
EM7004
125
Version: 2.0
6.5
Restoring the delivery state
Restoring the delivery state To restore the delivery state for backup objects in ELxxxx terminals, the CoE
object "Restore default parameters", SubIndex 001 can be selected in the TwinCAT System Manager
(Config mode) (see Fig.
“Selecting the ‘Restore default parameters’ PDO”
)
Fig. 145:
Selecting the "Restore default parameters" PDO
Double-click on SubIndex 001 to enter the Set Value dialog. Enter the value
1684107116
in field "Dec" or the
value
0x64616F6C
in field "Hex" and confirm with
OK
(Fig.
“Entering a restore value in the Set Value
dialog”
).
All backup objects are reset to the delivery state.
Fig. 146:
Entering a restore value in the Set Value dialog
Note
Alternative restore value
In some older terminals the backup objects can be switched with an alternative restore
value:Decimal value: "1819238756", Hexadecimal value: "0x6C6F6164"An incorrect entry
for the restore value has no effect.