Product overview
EM7004
15
Version: 2.0
2.4.1
Analog process data
In the delivery state the process data are shown in two's complement form (-1
dez
corresponds to 0xFFFF).
(channel 1),
3),
(channel 4) can be used to select other presentation types (e.g. magnitude sign format,
absolute value).
Output value
Output voltage
hexadecimal
decimal
0x8001
-32769
-10 V
0xC001
-16383
-5 V
0x0000
0
0 V
0x3FFF
+16383
+5 V
0x7FFF
+32767
+10 V
2.4.2
Process data equations
Calculation
The process data, which are transferred to the Bus Terminal, are calculated based on the following
equations:
Y
H
= X x A
K
+ B
K
Output value after manufacturer calibration (the feature object user scaling
[
(channel 2),
(channel 4) is inactive]
Y
A
= Y
H
x A
W
x 2
-16
+ B
W
Output value following user scaling