Product overview
EM7004
17
Version: 2.0
Sample: Limitation of the output range from -5 V to +5 V, calculation of the user
scaling GAIN factor
Y
A
= 16383
dec
corresponds to the desired upper limit value of +5
V
Y
H
= 32767
dec
corresponds to the upper limit value of +10 V
B
W
= 0
dec
corresponds to the offset of the user scaling
Y
A
= Y
H
x A
W
x 2
-16
+ B
W
Û (Y
A
- B
W
) / (Y
H
x 2
-16
) = A
W
(16383 - 0) / 32767 x 2
-16
=
A
W
= 32767
Calculation of the GAIN value for an upper limit value of +5 V
(corresponds to a lower limit value of -5 V through cancelling the sign)
corresponds to the user scaling gain factor (factor 0.5)
Sample: Shifting of the output range from -3 V to +10 V, calculation of the user
scaling OFFSET value
Y
A
= (- 9831
dec
)
corresponds to the desired lower limit value of -3 V
Y
H
= (-32769
dec
)
corresponds to the lower limit value of -10 V
A
W
= 65536
dec
corresponds to the gain factor of the user scaling (factor 1)
Y
A
= Y
H
x A
W
x 2
-16
+ B
W
Û Y
A
- Y
H
x A
W
x 2
-16
= B
W
(- 9831) - (- 32769 x 65536 x 2
-16
)
= B
W
= 22938
Calculation of the OFFSET value for the shifting of the lower limit value
to -3 V
corresponds to the offset value of the user scaling of +7 V
Note
OFFSET value
Shifting of the output value through the OFFSET is linear up to the lower (- 10 V) or upper
limit value (+ 10 V).
User-specific output value (user default output)
The analog output value can, e.g. in the case of a failure of communication with the controller, be set to a
user-specific value. The objects
(channel 1),
(channel 2),
(channel 3),
(channel 4) activate this option (value: TRUE); the output values are
determined with the objects
(channel 4). If this function is disabled (value of object
(channel 3),
FALSE), the manufacturer default value (0V) is output.
If the watchdog timer is deactivated (value of object
(channel 1),
(channel 4) is TRUE), no default value is
output.
PLS function (Programmable Limit Switch)
The PLS function enables a certain value ("PLS output data", object
digital outputs when the assigned encoder ("Encoder as PLS source", object
a particular switch value ("PLS switch value", object
). Object
mask") is used to specify which of the digital outputs are allocated to the PLS function.