Operation
EK1960
121
Version: 1.3.1
LED EC Link1 (green)
LED
State
Meaning
EC Link 1
off
No connection on the incoming EtherCAT segment
on
upstream EtherCAT device or EtherCAT Master connected
flashes
communication with upstream EtherCAT device or EtherCAT
Master
LED EC RUN (green)
Display
Meaning
permanently off
EtherCAT State INIT (Initialisation)
flashing uniformly
EtherCAT State PREOP (Pre-
Operational)
flashing slowly
EtherCAT State SAFEOP (Safe-
Operational)
permanently on
EtherCAT State OP (Operational)
flashing rapidly
EtherCAT State BOOT (Bootstrap
Modus)
LED EC Err (red)
The LED lights up red when there is an EtherCAT error.
LED EC Link2 (green)
LED
State
Meaning
EC Link 2
off
no connection to the downstream EtherCAT line
on
downstream EtherCAT device connected
flashes
Communication with downstream EtherCAT device
LED Splc (green/red) / FSoE
Splc (gre
en)
Splc (red) FSoE
Meaning
off
off
off
No safety-projekt on the EK1960
off
blink code
on
Error code of Safety Logic
1 - Function block error in Safety Logic
2 - Communication error in Safety Logic
4 - Other error in Safety Logic
(Combinations are possible, error code numbers are added)
off
permanent
flashing
on
Global Shutdown or Global Fault
blink code off
on
Safety Logic loaded but not in RUN
permanen
t flashing
off
on
Safety Logic loaded and in RUN
Customized Mode active
on
off
on
Safety Logic loaded and in RUN
Customized Mode NOT active
LED Us
The U
S
LED lights up as soon as the 24 V
DC
voltage is present at the U
S
connection.
Summary of Contents for EK1960 Series
Page 1: ...Operating Instructions for EK1960 TwinSAFE Compact Controller 1 3 1 2019 01 28 Version Date...
Page 2: ......
Page 6: ...Table of contents EK1960 6 Version 1 3 1...
Page 58: ...Operation EK1960 58 Version 1 3 1 Fig 51 Safety parameters of the input modules...
Page 140: ...Appendix EK1960 140 Version 1 3 1 5 2 Certificates...