Product description
EK1960
31
Version: 1.3.1
3.13
Address setting of the TwinSAFE compact controller
Fig. 9: Address selection switch of the EK1960
The TwinSAFE address of the controller must be set with the three rotary switches on the housing of the
EK1960 TwinSAFE controller. TwinSAFE addresses between 1 and 4095 are available.
Rotary switch
Address
1 (top)
2 (center)
3 (bottom)
0
0
1
1
0
0
2
2
0
0
3
3
…
…
…
…
0
0
F
15
0
1
0
16
0
1
1
17
…
…
…
…
0
F
F
255
1
0
0
256
1
0
1
257
…
…
…
…
F
F
F
4095
WARNING
TwinSAFE address
Each TwinSAFE address must be unique within a network!