Overview of input parameters
PrmName
Index
Meaning
Value
FSIN Module 9
Settings Common
80F0:00 Settings for input module 9 (inputs 17 - 18) This setting
exists only for modules 9 and 10
-
InputMode
80F0:03 Only input modules 9 and 10 support the parameters
Digital Mode On
and
Bumper Mode On
. All other modules
are set to
Digital Mode On
and cannot be changed by the
user.
- Digital Mode On
- Bumper Mode On
FSIN Module 1
Settings Channel
8071:00 Settings for input module 1 (inputs 01 - 02)
-
Channel1.
InputFiltertime
8071:01 Filter time for an input in the unit 100 µs. After the expiry
of this time the signal state is transmitted to the logic on
an edge change at the input. This value must be adapted
to the length of the test pulses if they are used.
10 (1 ms)
Channel1.
DiagTestPulse
FilterTime
8071:02 Filter time for an input in the unit 100 µs. This time must
elapse before a measurement of the momentary signal
state is carried out after an edge change. This value
should be adapted to the length of the test pulses if they
are used.
3 (300 µs)
Channel1.
TestPulse Diag
Mode
8071:03 The output channel from which the test pulse is expected
must be set here
External Testpulse
or drop-down list of
the EK1960
outputs
Channel2.
InputFiltertime
8071:04 Filter time for an input in the unit 100 µs. After the expiry
of this time the signal state is transmitted to the logic on
an edge change at the input. This value must be adapted
to the length of the test pulses if they are used.
10 (1 ms)
Channel2.
DiagTestPulse
FilterTime
8071:05 Filter time for an input in the unit 100 µs. This time must
elapse before a measurement of the momentary signal
state is carried out after an edge change. This value
should be adapted to the length of the test pulses if they
are used.
3 (300 µs)
Channel2.
TestPulse Diag
Mode
8071:06 The output channel from which the test pulse is expected
must be set here
External Testpulse
or drop-down list of
the EK1960
outputs
Corresponding parameters are available for input modules 1 to 10 (inputs 01 to 20) under the indices 8071:0
to 80E1:0 (in 10
hex
steps - 8071, 8081, 8091, 80A1 and so on).
The input modules 9 and 10 have additional parameters under indices 80F0:0 and 8100:0 with which the
operation modes
Digital Mode On
and
Bumper Mode On
can be set.
Summary of Contents for EK1960 Series
Page 1: ...Operating Instructions for EK1960 TwinSAFE Compact Controller 1 3 1 2019 01 28 Version Date...
Page 2: ......
Page 6: ...Table of contents EK1960 6 Version 1 3 1...
Page 58: ...Operation EK1960 58 Version 1 3 1 Fig 51 Safety parameters of the input modules...
Page 140: ...Appendix EK1960 140 Version 1 3 1 5 2 Certificates...