Product description
EK1960
21
Version: 1.3.1
Product designation
EK1960
Climate category according to EN 60721-3-3
3K3
(the deviation from 3K3 is possible only with optimal
environmental conditions and also applies only to the
technical data which are specified differently in this
documentation)
Permissible level of contamination
according to EN 60664-1
level of contamination 2
(comply with the chapter
)
Inadmissible operating conditions
TwinSAFE controllers must not be used under the
following operating conditions:
• under the influence of ionizing radiation (exceeding the
natural background radiation)
• in corrosive environments
• in an environment that leads to impermissible soiling of
the controller
Vibration / shock resistance
conforms to EN 60068-2-6 / EN 60068-2-27
EMC immunity/emission
conforms to EN 61000-6-2 / EN 61000-6-4
Shocks
15 g with pulse duration 11 ms in all three axes
Protection class as per IEC 60529
IP20
Permitted operating environment
In the control cabinet or terminal box, with minimum
protection class IP54 according to IEC 60529
Correct installation position
see chapter
Installation position and minimum distances
Technical approvals
CE, TÜV SÜD
NOTE
Protective circuit
No protective circuit is integrated in the output circuit of the EK1960, so it is necessary to provide a free-
wheeling diode on the actuator for inductive loads. However, it must be borne in mind that the free-wheeling
diode may prolong the switch-off times of the actuator.
The protective circuit must limit the induced voltage at the output to an amount of less than 29V. Thus, R/C
circuits and varistors are typically unsuitable.
Summary of Contents for EK1960 Series
Page 1: ...Operating Instructions for EK1960 TwinSAFE Compact Controller 1 3 1 2019 01 28 Version Date...
Page 2: ......
Page 6: ...Table of contents EK1960 6 Version 1 3 1...
Page 58: ...Operation EK1960 58 Version 1 3 1 Fig 51 Safety parameters of the input modules...
Page 140: ...Appendix EK1960 140 Version 1 3 1 5 2 Certificates...