Product description
EK1960
26
Version: 1.3.1
Logic parameters
Value
PFH
D
5.18 E-09
PFD
G
4.32 E-05
MTTF
D
high
DC
avg
high
Performance Level
PL e
Category
4
SIL
3
Output safety parameters
The following table contains the safety parameters for the digital output of the EK1960. This must be added
to the input and logic value to determine the total PFH value.
Digital output parameters
Value
PFH
D
1.5 E-10
PFD
G
2.62 E-07
MTTF
D
high
DC
avg
high
Performance Level
PL e
Category
4
SIL
3
Examples of safety loops
Characteristic numbers
Sample 1
Sample 2
Sample 3
Sample 4
Safety mat input
PLd, Cat. 2 8.48 E-10
8.48 E-10
8.48 E-10
8.48 E-10
Digital input
PLe, Cat. 4 6.4 E-11
6.4 E-11
Logic
PLe, Cat. 4 5.18 E-09
5.18 E-09
5.18 E-09
5.18 E-09
5.18 E-09
Digital output
PLe, Cat. 4 1.5 E-10
1.5 E-10
1.5 E-10
Relay output
(Cat. 4)
PLe, Cat. 4 1.46 E-09
1.46 E-09
Relay output
(Cat. 2)
PLd, Cat. 2 7.25 E-10
7.25 E-10
Overall result
PFH
D
/ Performance
Level / Category
6.18 E-09
PLd, Cat. 2
5.39 E-09
PLe, Cat. 4
7.49 E-09
PLd, Cat. 2
6.75 E-09
PLd, Cat. 2
3.8
Error response times
The error response times depend, among other things, on the logic program used and the settings of the
MultiplierDiagTestPulse
and
ModuloDiagTestPulse
parameters.
An error reaction for the tests of the I/O signals is realized by a weighted counter, therefore the switch-off
does not occur immediately at the first error of the diagnostic tests.
The maximum error reaction time results from the duration of the longest lasting test, this is the RAM test
and this is several hours.
Summary of Contents for EK1960 Series
Page 1: ...Operating Instructions for EK1960 TwinSAFE Compact Controller 1 3 1 2019 01 28 Version Date...
Page 2: ......
Page 6: ...Table of contents EK1960 6 Version 1 3 1...
Page 58: ...Operation EK1960 58 Version 1 3 1 Fig 51 Safety parameters of the input modules...
Page 140: ...Appendix EK1960 140 Version 1 3 1 5 2 Certificates...