Product description
EK1960
20
Version: 1.3.1
3.6
Technical data
Product designation
EK1960
Number of inputs
20
Number of outputs
24 (+ 4 optional relay outputs)
Cable length between sensor and input
30 m (if cables with a cross-sectional area of 0.75 mm²
are used)
Cable length between output and actuator
30 m (if cables with a cross-sectional area of 0.75 mm²
are used)
Minimum/maximum logic cycle time
approx. 1 ms / according the project size
Fault response time
≤ watchdog times
Watchdog time
min. 2 ms, max. 60,000 ms
Input process image
Dynamic, according to the TwinSAFE configuration in
TwinCAT 3
Output process image
Dynamic, according to the TwinSAFE configuration in
TwinCAT 3
Supply voltage (SELV/PELV)
24 V
DC
(–15% / +20%)
Provide a 2 A fuse for U
S
and U
P
E-bus power supply (5 V)
max. 500 mA
(In the case of higher current consumption,
please use the
power feed terminals in addition!)
Signal voltage inputs
Characteristic curve of the inputs [
Output module (4 channels)
24 V
DC
(–15% / +20%) SELV/PELV for U
P1
to U
P6
max. 2 A per channel
min. 30 mA with a test pulse length of 400 µs and
resistive load
Simultaneity factor 50% per module
Provide 5 A fuse for each U
Px
Diagnostic thresholds:
> 4 V -> high signal is detected
< 2.4 V -> low signal is detected
Permissible actuators
• inductive loads (see also
(A free-wheeling diode must be provided on the load)
• resistive loads
• capacitive loads
Current consumption of the modular electronics
at 24 V
DC
(without current consumption of
sensors/actuators)
U
S
typ. 80 mA
U
P
typ. 2 mA
U
P1
to U
P6
each typ. 2 mA
Dimensions (W x H x D)
230.5 mm x 100 mm x 58.6 mm
Weight
approx. 560 g (EK1960-260x) /
approx. 500 g (EK1960-000x)
Permissible ambient temperature (operation)
-25 °C to +55 °C
Permissible ambient temperature (transport/
storage)
-40 °C to +70 °C
Permissible humidity
5% to 95%, non-condensing
permissible air pressure
(operation/storage/transport)
750 hPa to 1100 hPa
(this corresponds to an altitude of approx. -690 m to
2450 m above sea level, assuming an international
standard atmosphere)
Summary of Contents for EK1960 Series
Page 1: ...Operating Instructions for EK1960 TwinSAFE Compact Controller 1 3 1 2019 01 28 Version Date...
Page 2: ......
Page 6: ...Table of contents EK1960 6 Version 1 3 1...
Page 58: ...Operation EK1960 58 Version 1 3 1 Fig 51 Safety parameters of the input modules...
Page 140: ...Appendix EK1960 140 Version 1 3 1 5 2 Certificates...