Operation
EK1960
129
Version: 1.3.1
4.17
Sync-Manager Configuration
Depending on the size of the TwinSAFE project on the TwinSAFE logic, it may be necessary to adjust the
sync manager configuration.
As soon as the following message appears during the saving or downloading of the project, the sync
manager configuration for the device has to be adapted.
Fig. 172: Overlapping Sync Manager
Adapting the Sync-Manager configuration
The Sync Manager settings can be made via the
Advanced Settings...
of the TwinSAFE logic.
Fig. 173: EtherCAT Advanced Settings
To calculate the smallest start address of SM3, the length of SM2 is multiplied by 3 and added to the start
address of SM2.
Start SM3 >= Start SM2 + 3* Length SM2
In addition, the starting address, together with 3 times the length of SM3, must not be larger than the
address 0x3000.
Start SM3 + 3* Length SM3 <= 0x3000